Output Frequency Detection - Mitsubishi Electric FR-A820-00046 Instruction Manual

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
5.11.7

Output frequency detection

The inverter output frequency is detected and output as output signals.
Pr.
41
M441
42
M442
43
M443
50
M444
116
M445
865
M446
870
M400
Output up-to-frequency sensitivity (SU signal, Pr. 41)
● Up to frequency (SU) is output when the output frequency reaches the set frequency.
● The Pr. 41 value can be adjusted within the range ±1% to ±100% considering the set frequency
as 100%.
● This parameter can be used to check that the set frequency has been reached, and provide signals
such as the operation start signal for related equipment.
SU
FR-A800
Name
Up-to-frequency
sensitivity
Output frequency
detection
Output frequency
detection for reverse
rotation
Second output frequency
detection
Third output frequency
60 Hz 50 Hz
detection
Low speed detection
Speed detection
hysteresis
Set frequency
Adjustment
range Pr. 41
OFF
OFF
ON
(M) Monitor display and monitor output signal
Initial value
Setting range Description
FM
CA
10%
0 to 100%
6 Hz
0 to 590 Hz
0 to 590 Hz
9999
9999
30 Hz
0 to 590 Hz
0 to 590 Hz
1.5 Hz
0 to 590 Hz
0 Hz
0 to 5 Hz
Fig. 5-170:
Output of the SU signal
Time
Set the level where the SU signal turns ON.
Set the frequency where the FU (FB) signal turns
ON.
Set the frequency where the FU (FB) signal turns
ON in reverse rotation.
Same as the Pr. 42 setting.
Set the frequency where the FU2 (FB2) signal
turns ON.
Set the frequency where the FU3 (FB3) signal
turns ON.
Set the frequency where the LS signal turns ON.
Set the hysteresis width for the detected
frequency.
I002626E
5 - 373