Mitsubishi Electric FR-A820-00046 Instruction Manual page 599

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
Fault output (Pr. 573 = "2")
● When the analog current input becomes 2 mA or lower, 4 mA input fault (E.LCI) will be activated
and the output is shut off.
● PID control (reverse action)
Output frequency
Fig. 5-205:
Fault output after deceleration to stop (Pr. 573 = "3")
● When the analog current input becomes 2 mA or lower, 4 mA input fault (E.LCI) will be activated
after the deceleration stop and the output is shut off.
● When the analog current input is restored during the deceleration, it will accelerate again and
operate according to the current input.
● PID control (reverse action)
Output frequency
Fig. 5-206:
FR-A800
20 mA
Set point (fixed)
Measured value
4 mA
STF
LF signal
PID signal
ALM signal
Fault output (Pr. 573 = 2)
20 mA
Set point (fixed)
Measured value
4 mA
STF
LF signal
PID signal
ALM signal
Fault output after deceleration to stop (Pr. 573 = 3)
(T) Multi-Function Input Terminal Parameters
E.LCI occurs
Input current
decrease
Return
3 mA
2 mA
Decelerates as the input current is lost
After deceleration stop, E.LCI occurs
Input current
decrease
Return
3 mA
2 mA
Time
I002650E
Time
I002651E
5 - 419

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents