Mitsubishi Electric FR-A820-00046 Instruction Manual page 624

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

(C) Motor constant parameters
Setting
● To perform tuning, set the following parameters about the motor.
First
motor Pr.
80
81
800
9
83
84
71
96
Tab. 5-174: Set the parameters before performing tuning
Differs according to the voltage class. (200 V/400 V)
For the settings for the SF-V5RU refer to page 2-74.
According to the Pr. 71 setting, the range of the motor constant parameter setting values and units
can be changed. Set the Pr. 71 "Applied motor setting" according to the motor to be used and the
motor constant setting range. (For other setting values of Pr. 71, refer to page 5-434.)
5 - 444
Second
Name
motor Pr.
453
Motor capacity
Number of motor
454
poles
Control method
451
selection
Electronic thermal O/L
51
relay
456
Rated motor voltage
Rated motor
457
frequency
450
Applied motor
Auto tuning setting/
463
status
Initial value
Description
9999 (V/F control) Set the motor capacity (kW).
9999 (V/F control) Set the number of motor poles (2 to 12).
Set this parameter when using vector control or Real
20
sensorless vector control.
Rated inverter
Set the rated motor current (A).
current
Set the rated motor voltage (V) printed on the
200 V/400 V
motor's rating plate.
Set the rated motor frequency (Hz).
9999
When the setting is "9999", the Pr. 3 "Base frequency"
setting is used.
Set this parameter according to the motor.
0 (standard
Three types of motor constant setting ranges, units
motor)
and tuning data can be stored according to settings.
Set "1" or "101".
1: Performs tuning without rotating the motor.
(Excitation noise occurs at this point.)
0
101: Performs tuning without rotating the motor.
The motor can rotate up to the speed near the rated
motor frequency.
Parameters