Reference - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

Default I/O connections
1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(2...10 V voltage
signal).
1) Hand: frequency reference comes from the
integrated potentiometer
PID: Process reference comes from the
integrated potentiometer.
3)
I/O connection
SCR
Signal cable shield (screen)
AI
Process actual value: 4...20 mA
GND
Analog input circuit common
2)
+10V
Reference voltage: +10 VDC, max. 10 mA
+24V
Auxiliary voltage output: +24 VDC, max. 200 mA
GND
Auxiliary voltage output common
DCOM
Digital input common
DI1
Stop (0) / Start (1) (Hand)
DI2
Hand (0) / PID (1) control selection
DI3
Constant speed 1: parameter 1202
DI4
Run enable
DI5
Stop (0) / Start (1) (PID)
4)
Relay connection
COM
NC
NO
1)
Relay output
No fault [Fault (-1)]
2) 360 degree grounding under a clamp.
3) Tightening torque = 0.22 N·m / 2 lbf. in
4) Tightening torque = 0.5 N·m / 4.4 lbf. in.
3