Parameters In The Short Parameter Mode; Start-Up Data; Select - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

66

Parameters in the Short Parameter mode

The following table describes the parameters that are visible in the Short Parameter
mode. See section
mode. All parameters are presented in detail in section
Parameter
Parameters in the Short Parameter mode
No.
Name/Value

99 START-UP DATA

9902
APPLIC MACRO
1 = ABB STANDARD
2 = 3-WIRE
3 = ALTERNATE
4 = MOTOR POT
5 = HAND/AUTO
31 = LOAD FD SET
9905
MOTOR NOM VOLT
100...300 V (200 V /
US: 230 V units)
230...690 V (400 V /
US: 460 V units)
9906
MOTOR NOM CURR
0.2...2.0 · I
2N
Actual signals and parameters
Parameter modes
mode, starting on page 72.
Description
Application macro. Definition of motor set-up data.
Selects the application macro or activates FlashDrop parameter values. See
chapter
Application
macros.
Standard macro for constant speed applications
3-wire macro for constant speed applications
Alternate macro for start forward and start reverse applications
Motor potentiometer macro for digital signal speed control applications
Hand/Auto macro to be used when two control devices are connected to the
drive:
- Device 1 communicates through the interface defined by external control
location EXT1.
- Device 2 communicates through the interface defined by external control
location EXT2.
EXT1 or EXT2 is active at a time. Switching between EXT1/2 through digital
input.
FlashDrop parameter values as defined by the FlashDrop file.
FlashDrop is an optional device for fast copying of parameters to unpowered
drives. FlashDrop allows easy customisation of the parameter list, e.g.
selected parameters can be hidden. For more information, see MFDT-01
FlashDrop User's Manual [3AFE68591074 (English)].
Defines the nominal motor voltage. Must be equal to the value on the motor
rating plate. The drive cannot supply the motor with a voltage greater than
the input power voltage.
Output voltage
9905
WARNING! Never connect a motor to a drive which is connected to power
line with voltage level higher than the rated motor voltage.
Voltage.
Note: The stress on the motor insulations is always dependent on the drive
supply voltage. This also applies to the case where the motor voltage rating
is lower than the rating of the drive and the supply of the drive.
Defines the nominal motor current. Must be equal to the value on the motor
rating plate.
Current
on page
53
for how to select the parameter
Parameters in the Long
Output frequency
9907
Def
1 = ABB
STANDARD
200
(US: 230)
400
(US: 460)
I
2N