GE C60 Instruction Manual page 392

Breaker protection system
Hide thumbs Also See for C60:
Table of Contents

Advertisement

SYSTEM SETUP
the new command frame arrives within the five-second period, the FlexLogic operands are updated, and the five-second
timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active;
when disabled, all 16 operands for each aggregator remain reset.
Table 5-21: FlexLogic operands supported by aggregator
Operand type
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
as above
as above
as above
as above
5
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1(2)  90-5 AGGR 1(2)
CONFIGURATION
 90-5 AGGR 1
 CONFIGURATION
PMU AGGREGATOR 1 NAME
This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850
MSVID filed in the output stream. The field allows 65 characters, but uses the first 56 characters.
AGGREGATOR 1: PHYSICAL PORT
transmitted. The range is 1, 2, 3.
PMU AGGREGATOR 1: UDP PORT
A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR 1: NUMBER OF ASDUs
through to 4.
Table 5-22: Number of ASDUs
Settings for
Transmission
ASDU
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
5-184
Operand syntax
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
PMU AGGREGATOR 1
NAME:
PMU AGGREGATOR 1
PORT: 1
PMU AGGREGATOR 1
UDP PORT: 102
PMU AGGREGATOR 1
NUMBER OF ASDUs: 1
— A user-defined visible string of characters (maximum 56) to identify the source of the stream.
— This setting determines the physical ports through which the synchrophasor traffic is
— This setting selects the UDP port number that is used by this dataset for network reporting.
— This setting sets the number of Application Service Data Units (ASDUs) from 1
Operand description
Phasor data concentrator asserts control bit 1, as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Range: 56-character ASCII text (blank by default)
Range: 1, 2, 3
Range: 0 to 65534 in steps of 1
Range: 1 to 4
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL