Rxgoose Analogs; Sensitive Directional Power - GE C60 Instruction Manual

Breaker protection system
Hide thumbs Also See for C60:
Table of Contents

Advertisement

METERING
Table 6-2: FlexElement base units
Base unit
BREAKER ACC ARCING AMPS
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
FAULT LOCATION
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SENSITIVE DIR POWER
(Sns Dir Power)
SOURCE CURRENT
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)

6.4.6 RxGOOSE analogs

ACTUAL VALUES  METERING  RxGOOSE Analogs
 RxGOOSE
 Analogs
6
The C60 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.

6.4.7 Sensitive directional power

ACTUAL VALUES  METERING  SENSITIVE DIRECTIONAL POWER  DIRECTIONAL POWER 1(2)
 DIRECTIONAL
 POWER 1
The effective operating quantities of the sensitive directional power elements display here. The display is useful to calibrate
the feature by compensating the angular errors of the CTs and VTs with the use of the
6-22
Description
2
BASE = 2000 kA
× cycle
2
BASE = 1 kA
× cycle
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
BASE = Line Length as specified in Fault Report
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
P
= maximum value of 3 × V
BASE
BASE
for the sensitive power directional element(s).
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
DIRECTIONAL POWER 1
3Φ: 0.000 W
× I
for the +IN and –IN inputs of the sources configured
BASE
× I
for the +IN and –IN inputs
BASE
and
RCA
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
settings.
CALIBRATION