TARGETS MENU
To view error messages in EnerVista software:
1.
Access Actual Values > Records > Event Records.
7.2.2.2 Major self-test error messages
The major self-test errors are outlined in this section.
INCOMPATIBLE H/W:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: One or more installed hardware modules is not compatible with the C60 order code.
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
Latched target message: No.
Description of problem: The number or type of installed hardware modules does not match the order code stored in
the C60.
How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five
seconds.
What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If a
module has intentionally been added or removed, refresh the order code under Device Setup. If the problem persists,
contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
Latched target message: No.
Description of problem: A FlexLogic equation is incorrect.
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
What to do: Finish all equation editing and use self tests to debug any errors.
7
UNIT NOT PROGRAMMED:
Check Settings
Latched target message: No.
Description of problem: The
programmed.
How often the test is performed: On power up and whenever the
setting is altered
What to do: Program all settings and then set
DIAGNOSTIC FAILURE___:
Self Test Error
Latched target message: No.
Description of problem: Internal recovery failure detected.
How often the test is performed: Upon recovery.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
7-8
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
.
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS
setting indicates the C60 is not
to "Programmed."
.