GROUPED ELEMENTS
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.

5.7.3 Phase current

5.7.3.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT
 PHASE CURRENT
5
The C60 contains protection elements for phase time overcurrent (ANSI device 51P) and phase instantaneous overcurrent
(ANSI device 50P). A maximum of six phase time overcurrent and eight phase instantaneous overcurrent elements are
available, dependent on the CT/VT modules ordered with the relay. The following table has details.
5-212
 VOLTAGE ELEMENTS
 POWER
 PHASE TOC 1
 PHASE TOC 2
 PHASE TOC 3
 PHASE TOC 4
 PHASE TOC 5
 PHASE TOC 6
 PHASE IOC 1
 PHASE IOC 2
 PHASE IOC 3
 PHASE IOC 4
 PHASE IOC 5
 PHASE IOC 6
 PHASE IOC 7
 PHASE IOC 8
See page 5-239
See page 5-245
See page 5-218
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
See page 5-220
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL