Mitsubishi Electric FR-A820-00046 Instruction Manual page 753

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
● The set point/deviation input method can also be flexibly selected by Pr. 609 "PID set point/
deviation input selection" and the measured value input method can be selected by Pr. 610 "PID
measured value input selection". Selection by Pr. 609 and Pr. 610 is valid when Pr. 128 = "1000 to
2011".
Pr. 609 and Pr. 610 settings
Tab. 5-225: Setting of Pr. 609 and Pr. 610
When the same input method has been selected for the set point and measured value using Pr. 609
and Pr. 610, set point input is invalid. (The inverter runs at set point 0%)
NOTE
When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6
to prevent a minus voltage from being entered as the deviation input signal. Input of a minus volt-
age might damage devices and the inverter.
● The following shows the relationship between the input values of the analog input terminals and
set point, measured value and deviation. (Calibration parameter initial values)
Input
terminal
Terminal
2
Terminal
1
Terminal
4
Tab. 5-226: Relationship between the signals
Can be changed by Pr. 73 and Pr. 267 and the voltage/current input switch. (Refer to page 5-406.)
NOTE
Always perform calibration after changing the voltage/input specification with Pr. 73, Pr. 267, and
the voltage/current input selection switch.
FR-A800
1
2
3
4
5
Inspect
specification
Set point
0 V = 0%
0 to 5 V
5 V = 100%
0 V = 0%
0 to 10 V
10 V = 100%
0 mA = 0%
0 to 20 mA
20 mA = 100%
–5 V to 0 V = 0%
0 to ±5 V
5 V = +100%
–10 V to 0 V = 0%
0 to ±10 V
10 V = +100%
0 V to 1 V = 0%
0 to 5 V
5 V = 100%
0 V to 2 V = 0%
0 to 10 V
10 V = 100%
0 to 4 mA = 0%
0 to 20 mA
20 mA = 100%
Input method
Terminal 1
Terminal 2
Terminal 4
CC-Link communication
PLC function
Relationship with analog input
Result
0 V = 0%
5 V = 100%
0 V = 0%
10 V = 100%
0 mA = 0%
20 mA = 100%
–5 V to 0 V = 0%
5 V = +100%
–10 V to 0 V = 0%
10 V = +100%
0 V to 1 V = 0%
5 V = 100%
0 V to 2 V = 0%
10 V = 100%
0 to 4 mA = 0%
20 mA = 100%
(A) Application parameters
Calibration parameter
Deviation
0 V = 0%
5 V = 100%
0 V = 0%
Pr. 125, C2 to C4
10 V = 100%
0 V = 0%
20 mA = 100%
–5 V = –100%
0 V = 0%
When Pr. 128 = "10",
5 V = +100%
Pr. 125, C2 to C4.
When Pr. 128 ≥ "1000",
–10 V = –100%
C12 to C15.
0 V = 0%
10 V = +100%
0 V = –20%
1 V = 0%
5 V = 100%
0 V = –20%
1 V = 0%
Pr. 126, C5 to C7
10 V = 100%
0 V = –20%
4 mA = 0%
20 mA = 100%
5 - 551