CC-Link IE Field Network (FR-A800-GF)
Remote register (from the inverter to the master module)
Device No.
Signal
RWr0
Reply code
RWr2
Reply code
RWr4,
RWr5,
Reply code
RWr6
RWr10,
RWr12,
RWr14,
Reply code
RWr16,
RWr18,
RWr1A
RWr11,
RWr13,
RWr15,
Read data
RWr17,
RWr19,
RWr1B
RWr20
Error status
RWr21
Fault record (fault data)
RWr22
Fault record (output frequency)
RWr23
Fault record (output current)
RWr24
Fault record (output voltage)
RWr25
Fault record (energization time)
RWr26
First monitor value
RWr27
Second monitor value
RWr28
Third monitor value
RWr29
Fourth monitor value
RWr2A
Fifth monitor value
RWr2B
Sixth monitor value
RWr2C
Seventh monitor value
RWr2D
Eighth monitor value
RWr2E
Ninth monitor value
RWr2F
Tenth monitor value
RWr30 to
Monitor value
RWr7F
Tab. 5-349:
Remote register (inverter
5 - 756
Description
When "1" is set in RY21 or RY22, the following reply codes are set for the frequency
setting command. The setting value "0" is set normally, and a value other than "0" is
set at an error.
H0000: Normal
H0001: Write mode fault
H0003: Setting range fault
When "1" is set in RY23 or RY24, the following reply codes are set for the torque
command / torque limit. The setting value "0" is set normally, and a value other than
"0" is set at an error.
H0000: Normal
H0003: Setting range fault
When the PID command (RWw4 to RWw6) is set, the following reply code is set for the
PID command. The setting value "0" is set normally, and a value other than "0" is set at
an error.
H0000: Normal
H0003: Setting range fault
When "1" is set in RY25, the following reply codes corresponding to the instruction
code RWw10, 12, 14, 16, 18, and 1A are set. The setting value "0" is set normally, and a
value other than "0" is set at an error.
H0000: Normal
H0001: Write mode fault
H0002: Parameter selection fault
H0003: Setting range fault
For a normal reply, the reply data to the instruction specified by the instruction code
is set.
The setting value "0" is set during normal inverter operation, and the data code of the
corresponding error is set at an error. (For the data codes or details of fault records,
refer to page 6-5.)
The data code of faults history No. specified by RWw21 is stored in the lower 8bits.
Lower 8 bits of RWw21 will be reverted back to the upper 8 bits.
Output frequency of the faults history No. specified in RWw21 is stored.
Output current of the faults history No. specified in RWw21 is stored.
Output voltage of the faults history No. specified in RWw21 is stored.
Energization time of the faults history No. specified in RWw21 is stored.
When "1" is set in RY20, the monitored data specified by the monitor code RWw26 to
RWw2F is saved.
Output frequency, output current, and output voltage monitors are held at an
inverter failure.
Fixed monitored data are saved regardless of the RY20 setting.
Output frequency, output current, and output voltage monitors are held at an
inverter failure.
master module)