Control Panel
These output types mimic the zone inputs. The output operates when the zone is unsealed
and is reset when the zone is sealed. They operate regardless of the selected zone type Zone
type can not be "Not Used". This feature operates when the system is armed or disarmed.
4,5 Global Chime
This output operates when any Chime zones are activated. The output is reset when all Chime
zones are resealed.
4,6 Zone Not Sealed
This output operates when a Zone is unsealed. There are some conditions for the zone:
1> the zone type is valid, and is not chime, keyswitch
2> the zone is assigned to a valid partition
3> the zone is not bypassed
4,7 Zone Not Sealed after Exit Time
This output operates if a Zone is unsealed and the exit time of the partition which the zone
belongs to is end. There are some conditions for the zone:
The output is reset when all zones are sealed or the system is disarmed.
4,9 AC MAINS 60 Hz or 50 Hz
This output is activated when the AC MAINS supply frequency is 60 Hz. The output is reset if
the AC MAINS supply returns to 50 Hz.
Notice!
Output Event Types 4,10 through 6,1 are available only to partitioned control panels.
4,10 Area 1 Has Unsealed Zone
4,11 Area 2 Has Unsealed Zone
These two outputs operate when a zone in their corresponding area registers as unsealed
either when the area is armed in AWAY Mode or STAY Mode, or the area is disarmed. There are
some conditions for the zone:
Example
Zone 1 is allocated to Area 1. If Zone 1 is unsealed, Output Event Type 4,10 operates. The
output is reset when the zone is resealed.
5,2 Area 1 in Alarm
5,3 Area 2 in Alarm
These two outputs operate when a zone in their corresponding area registers an alarm. These
outputs are reset when a valid User Code is entered or Siren Run Time expires.
Example
Zone 1 is allocated to Area 1. If Zone 1 registers an alarm, Output Event Type 5,2 operates.
The output is reset when a valid User Code assigned to Area 1 is entered.
5,6 Area 1 Is Armed
5,7 Area 2 Is Armed
These two outputs operate when their corresponding area are armed in AWAY Mode or STAY
Mode 1 or STAY Mode 2. The output is reset when the corresponding area is disarmed.
Example
Bosch Security Systems, Inc.
the zone type is valid, and is not chime, keyswitch
the zone is assigned to a valid partition
the zone is not bypassed
the zone type is valid, and is not chime, keyswitch
the zone is assigned to a valid partition
the zone is not bypassed
Installation Guide
Programmable Outputs | en
2017.10 | 03 | F.01U.298.026
129