7) Room temperature sensor control for cooling (for other than Mini duct type)
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
Function number
30
In case of Slim duct type and Floor/Ceiling type models:
In floor console installations, select "01".
8) Room temperature sensor control for heating (for other than Mini duct type)
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
Function number
31
In case of Slim duct type and Floor/Ceiling type models:
In floor console installations, select "01".
9) Room temperature control for indoor unit sensor (for Mini duct type only)
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac-
turer's recommended value).
Function number
30
(For cooling)
(For heating)
Setting value
00
01
02
03
Setting value
00
01
02
03
Setting value
00
01
02
03
04
05
06
07
08
31
09
10
11
12
13
14
15
16
17
- 245 -
Setting description
Standard
Slightly lower control
Lower control
Higher control
Setting description
Standard
Lower control
Slightly higher control
Higher control
Setting description
Standard setting
No correction 0.0 °C
-0.5 °C
-1.0 °C
-1.5 °C
-2.0 °C
More cooling
Less heating
-2.5 °C
-3.0 °C
-3.5 °C
-4.0 °C
+0.5 °C
+1.0 °C
+1.5 °C
+2.0 °C
Less cooling
More heating
+2.5 °C
+3.0 °C
+3.5 °C
+4.0 °C
Factory setting
Factory setting
Factory
setting