ABB Relion RES670 Operator's Manual
ABB Relion RES670 Operator's Manual

ABB Relion RES670 Operator's Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

®
Relion
670 series
Phasor measurement unit RES670
Operator's manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion RES670

  • Page 1 ® Relion 670 series Phasor measurement unit RES670 Operator's manual...
  • Page 3 Document ID: 1MRK511251-UEN Issued: February 2015 Revision: B Product version: 1.2 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............9 Introduction to the operator’s manual..........9 About the complete set of manuals for an IED......9 About the operator’s manual............10 Intended audience...............11 Related documents..............11 Revision notes................12 Section 2 Safety information............13 Warnings..................13 Section 3 Overview................15 Operator overview................15 Identify the IED.................15 Section 4 Understand the IED local human-machine...
  • Page 8 Table of contents View analog mean values..............28 Overview..................28 mA input module MIM............28 View monitoring values..............28 Service values CVMMXN............28 Current phasors CMMXU............29 Voltage phasors VMMXU/VNMMXU...........29 Current sequence component CMSQI........29 Voltage sequence component VMSQI........29 View metering values...............29 Pulse counter logic PCGGIO............29 Function for energy calculation and demand handling ETPMMTR...................30 Section 7 Event list.................31 View events..................31...
  • Page 9 Table of contents Communication................37 Overview................37 Station communication............37 Ethernet configuration............38 Analog and I/O modules..............39 Overview................39 Analog modules..............39 I/O modules................39 HMI....................40 Overview................40 LEDs..................40 Screen ...................40 Functions................40 Change lock ................41 Control..................41 Apparatus control..............41 Control commands..............41 Monitoring..................42 Overview................42 Service values CVMMXN............42 Current phasors CMMXU............42 Voltage phasors VMMXU/VNMMXU........42 Current sequence components CMSQI ........43 Voltage sequence components VMSQI ........43...
  • Page 10 Table of contents Voltage protection................46 Overview................46 Two step overvoltage protection OV2PTOV ......46 Two step undervoltage protection UV2PTUV ......46 Frequency protection..............47 Overview................47 Overfrequency protection SAPTOF ........47 Rate-of-change frequency protection SAPFRC ....47 Underfrequency protection SAPTUF ........47 Multipurpose protection...............47 Overview................47 General current and voltage protection CVGAPC....48 Secondary system supervision............48 Overview................48 Current circuit supervision CCSRDIF ........48...
  • Page 11 Table of contents Function test modes.................55 Overview..................55 Current protection................55 Voltage protection ...............55 Frequency protection..............56 Multipurpose protection ..............56 Secondary system protection .............56 Control ..................56 Monitoring..................56 Logic....................56 Function status.................56 Current protection................56 Four step directional negative phase sequence overcurrent protection NS4PTOC..........57 Four step phase overcurrent protection OC4PTOC....57 Four step residual overcurrent protection EF4PTOC.....57 Sensitive directional residual over current and power protection SDEPSDE.............57...
  • Page 12 Table of contents LEDs..................62 Measured value expander block RANGE_XP......62 IEC61850 generic communication I/O functions SPGGIO.................62 Logic....................62 Boolean 16 to Integer conversion B16IFCVI, B16I....62 Integer to Boolean 16 conversion IB16FCVB, IB16....63 Tripping logic SMPPTRC ............63 Trip matrix logic TMAGGIO............63 Logic gate................63 Logic SR/RS memory.............63 Logic timer set................63 Communication................64...
  • Page 13 Table of contents Section 15 Glossary.................79 Operator's manual...
  • Page 15: Section 1 Introduction

    Section 1 1MRK511251-UEN B Introduction Section 1 Introduction About this chapter This chapter is an introduction to the operator’s manual, its purpose and usage. Introduction to the operator’s manual 1.1.1 About the complete set of manuals for an IED The user’s manual (UM) is a complete set of five different manuals: Engineeringmanual Installation and Commissioning manual...
  • Page 16: About The Operator's Manual

    Section 1 1MRK511251-UEN B Introduction manual should be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The Installation and Commissioning Manual (ICM) contains instructions on how to install and commission the protection IED. The manual can also be used as a reference during periodic testing.
  • Page 17: Intended Audience

    670 series SPA and signal list 1MRK 500 092-WEN IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN Engineering manual 670 series 1MRK 511 240-UEN Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation. Operator's manual...
  • Page 18: Revision Notes

    Section 1 1MRK511251-UEN B Introduction 1.1.5 Revision notes Revision Description First issue for 670 series version 1.2. Maintenance updates, PR corrections Maintenance updates, PR corrections Operator's manual...
  • Page 19: Section 2 Safety Information

    Section 2 1MRK511251-UEN B Safety information Section 2 Safety information About this chapter This chapter lists warnings and cautions that must be followed when handling the IED. Warnings Do not touch circuitry during operation. Potentially lethal voltages and currents are present. Always connect the IED to protective earth, regardless of the operating conditions.
  • Page 21: Section 3 Overview

    Section 3 1MRK511251-UEN B Overview Section 3 Overview About this chapter This chapter presents a general overview of the Operator's manual. Operator overview The Local human-machine interface (LHMI) on the IED provides an ideal mechanism for the day to day operation and even advanced use of the IED. The keypad, LCD and LEDs on the front of the IED are what constitute the LHMI.
  • Page 22 Section 3 1MRK511251-UEN B Overview IEC10000336-1-en.vsd IED10000336 V1 EN Figure 1: Typical example of product identifier screen on local HMI IEDProdType is the Relion 670 series product type (REB, REC, RED, REG, REL, RET and so on) ProductDef specifies the version of the product, in the following order: major version.
  • Page 23 Section 3 1MRK511251-UEN B Overview IEC10000337-1-en.vsd IEC10000337 V1 EN Figure 2: Typical example of IED product type and version properties in PCM600 FirmwareVer Specifies the version of the product firmware IEDMainFunType Specifies the main IED functionality, in accordance to IEC60870-5-103 numbering: •...
  • Page 25: Section 4 Understand The Ied Local Human-Machine Interface

    Section 4 1MRK511251-UEN B Understand the IED local human-machine interface Section 4 Understand the IED local human- machine interface About this chapter This chapter describes the display, its keys (buttons) and LEDs that make up the local HMI on the IED. How the keys are used to navigate the HMI, how to interpret the graphic information on the LCD and, what the LEDs indicate is explained in the sections that follow.
  • Page 26 Section 4 1MRK511251-UEN B Understand the IED local human-machine interface IEC05000153 V1 EN Figure 4: The HMI keypad. Table describes the HMI keys that are used to operate the IED. Table 1: HMI keys on the front of the IED Function Press to close or energize a breaker or disconnector.
  • Page 27: Key Activated Screens

    Section 4 1MRK511251-UEN B Understand the IED local human-machine interface Function Press to navigate backwards between screens and move left in editing mode. IEC05000110 V1 EN Press to move up in the single line diagram and in the menu tree. IEC05000111 V1 EN Press to move down in the single line diagram and in the menu tree.
  • Page 28: Led

    Section 4 1MRK511251-UEN B Understand the IED local human-machine interface This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28 lines with up to 40 characters per line. 4.5.1 Introduction The LED module is a unidirectional means of communicating. This means that events may occur that activate a LED in order to draw the operators attention to something that has occurred and needs some sort of action.
  • Page 29: Local Hmi Setup

    Section 4 1MRK511251-UEN B Understand the IED local human-machine interface • Bay controller failure • CB close blocked • Interlocking bypassed • SF6 Gas refill • Position error • CB spring charge alarm • Oil temperature alarm • Thermal overload trip The RJ45 port has a yellow LED indicating that communication has been established between the IED and a computer.
  • Page 30: Change

    Section 4 1MRK511251-UEN B Understand the IED local human-machine interface 4.7.2 Change To change a parameter setting the following steps should be followed: Navigate to the desired parameter or quantity using the arrow keys. Press the E key when the parameter to be changed is highlighted. Move between digits or letters using the left and right arrow keys.
  • Page 31: Section 5 Understand The Hmi Tree

    Section 5 1MRK511251-UEN B Understand the HMI tree Section 5 Understand the HMI tree About this chapter This chapter describes the structure of the HMI. The main menu includes submenus such as Measurements, Events, Disturbance Report, Settings, Diagnostics, Test and Reset. These branch out into a typical tree structure. Overview The local HMI has the following main menu: •...
  • Page 33: Section 6 Read Measured Values

    Section 6 1MRK511251-UEN B Read measured values Section 6 Read measured values About this chapter This chapter describes measurement categories and how to locate them using the HMI. Each measurement category has a section of its own that includes a general description of the type of quantity being measured and the path in the local HMI to the measurement.
  • Page 34: View Analog Primary Values

    Section 6 1MRK511251-UEN B Read measured values View analog primary values 6.2.1 Overview The analog primary values are analog quantities measured on the primary side of the TRM and reflect the actual current or voltage on the primary side of the CTs. The ratio is adjusted under settings and also depends on the rating of the TRM.
  • Page 35: Current Phasors Cmmxu

    Section 6 1MRK511251-UEN B Read measured values 6.5.2 Current phasors CMMXU Main menu/Measurement/Monitoring/CurrentPhasors(MMXU)/CMMXU:x All three phase currents and their phase angles are displayed here. 6.5.3 Voltage phasors VMMXU/VNMMXU Main menu/Measurements/Monitoring/VoltagePhasors(MMXU)/Phase - Phase/VMMXU:x Phase to phase voltages and phase angles are displayed here. Main menu/Measurement/Monitoring/VoltagePhasors(MMXU)/Phase - Earth/ VNMMXU:x Phase to earth voltages and phase angles are displayed here.
  • Page 36: Function For Energy Calculation And Demand Handling Etpmmtr

    Section 6 1MRK511251-UEN B Read measured values The output data generated from the pulse counter function include data about the status of the counter and counter values. 6.6.2 Function for energy calculation and demand handling ETPMMTR Main menu/Measurements/Metering/ThreePhEnergMeas(MMTR)/ ETPMMTR:x The output data generated from the energy measuring function includes active forward/reverse energy and reactive forward/reverse energy.
  • Page 37: Section 7 Event List

    Section 7 1MRK511251-UEN B Event list Section 7 Event list About this chapter This chapter describes how to find and read the event list. View events 7.1.1 Overview Events displays recorded events such as trips and breaker opened or closed. Main menu/Events Displays a list of events in chronological order and where each event has a time stamp.
  • Page 39: Section 8 Handle Disturbances

    Section 8 1MRK511251-UEN B Handle disturbances Section 8 Handle disturbances About this chapter This chapter describes disturbance detection and handling. This includes resetting LED alarms, triggering disturbance reports and the viewing of several fault indicators. Identify a disturbance A disturbance record can be generated manually by using the Manual Trig functionality in the HMI menu.
  • Page 40: View Trip Values

    Section 8 1MRK511251-UEN B Handle disturbances Main menu/Disturbance records/Record xx/Event recording 8.2.4 View trip values In the Trip values section of a disturbance recording both the pre-fault and the fault values for current can be viewed. The recording number and Trig time are also displayed.
  • Page 41: Section 9 Read And Change Settings

    Section 9 1MRK511251-UEN B Read and change settings Section 9 Read and change settings About this chapter This chapter describes how to find and change settings and parameters. The chapter is divided into two sections which match the way the two categories of settings are divided up in the HMI.
  • Page 42: Timesynchbin

    Section 9 1MRK511251-UEN B Read and change settings Here the parameters FineSyncSource, CourseSyncSrc and SyncMaster are switched on or off. 9.1.2.3 TIMESYNCHBIN Main menu/Settings/Time/Synchronization/SYNCHBIN:x Binary input synchronization settings available here are the position of the of the module, the number of the binary input and the detection mode. 9.1.2.4 DSTBEGIN Main menu/Settings/Time/Synchronization/DSTBEGIN:x...
  • Page 43: Power System

    Section 9 1MRK511251-UEN B Read and change settings The IED must be in setting group 1 before changing settings in General settings 9.2.1 Power system 9.2.1.1 Overview Under Power system in General settings there are four parameter categories. These are Identifiers, Primary values, three phase analog group and three phase analog sum group.
  • Page 44: Ethernet Configuration

    Section 9 1MRK511251-UEN B Read and change settings Includes available instances of GOOSE binary receive (GOOSEBINRCV) where setting Operation can be set On or Off. IEC61850–8–1 Main menu/Settings/General settings/Communication/Station communication/ IEC61850–8–1 Includes settings for the IED name,Operation (On/Off) and GOOSE. Multicommand send Main menu/Settings/General settings/Communication/Station communication/ MultiCommandSend/MULTICMDSND:x...
  • Page 45: Analog And I/O Modules

    Section 9 1MRK511251-UEN B Read and change settings Main menu/Settings/General settings/Communication/Ethernet configuration/ Rear OEM-Port CD The IP address (with different IP address when a second channel is used), IP mask and Mode for the Optical Ethernet Module (OEM) at the rear of the IED are set here. Main menu/Settings/General settings/Communication/Ethernet configuration/ Rear OEM - Redundant PRP Redundant station bus communication IEC61850-8-1 are set here.
  • Page 46: Hmi

    Section 9 1MRK511251-UEN B Read and change settings Main menu/Settings/General Settings/I/O Modules Settings for binary inputs and outputs (BIM, BOM, IOM), and under each binary module there are one or more adjustable parameters. In the I/O modules folder there is also a “reconfigure” setting that starts a dialog box prompting the user to confirm or cancel the command.
  • Page 47: Change Lock

    Section 9 1MRK511251-UEN B Read and change settings 9.2.4.5 Change lock Main menu/Settings/General settings/HMI/Change lock The operation of the Change lock function can be activated or deactivated here. 9.2.5 Control 9.2.5.1 Apparatus control Overview Under Control in General settings, parameters for Apparatus control can be adjusted.
  • Page 48: Monitoring

    Section 9 1MRK511251-UEN B Read and change settings Logic rotating switch SLGGIO Main menu/Settings/General settings/Control/Commands/ SelectorSwitch(GGIO)/SLGGIO:x A number of selector switches SLGGIO can be configured in the system. These are substitutes for rotating physical switches. The parameter setting StopAt Extremesis used to disable or enable the end position of the switch.
  • Page 49: Current Sequence Components Cmsqi

    Section 9 1MRK511251-UEN B Read and change settings Main menu/Settings/General Settings/Monitoring/VoltagePhasors(NMMXU)/ Phase-Earth/VNMMXU:x Displays available instances of the voltage phasor function VNMMXU with output data for phase to earth voltage, (amplitude, phase angle). The setting parameters for supervision levels, deadband etc. are set here. 9.2.6.5 Current sequence components CMSQI Main menu/Settings/General settings/Monitoring/Current sequence...
  • Page 50: Fault Locator Lmbrflo

    Section 9 1MRK511251-UEN B Read and change settings Analog signals Main menu/Settings/General settings/Monitoring/Disturbance report/Analog signals(RADR)/Channel xx-yy There are some groups of a number of channels with a number of analog signals per channel. Each signal has some settable parameters such as operation, Nominal value and trig values.
  • Page 51: Pulse Counter Logic Pcggio

    Section 9 1MRK511251-UEN B Read and change settings 9.2.7.2 Pulse counter logic PCGGIO Main menu/Settings/General settings/Metering/PulseCounter(PCGGIO)/ PCGGIO:x In the Pulse counter PCGGIO folder there are a number of instances of the pulse counter function PCGGIO. Each instance has a setting and some settable parameters.
  • Page 52: Four Step Phase Overcurrent Protection Oc4Ptoc

    Section 9 1MRK511251-UEN B Read and change settings 9.3.2.3 Four step phase overcurrent protection OC4PTOC Main menu/Settings/Setting Group N/Current protection/ PhaseOverCurrent4Step(PTOC,51_67)/OC4PTOC:x Displays some instances of OC4PTOC each with several settings. The settings range from base current and voltage settings to parameters for customer programmable curves.
  • Page 53: Frequency Protection

    Section 9 1MRK511251-UEN B Read and change settings Displays available settable parameters. The operation mode, the operate voltage as percentage of Ubase are examples of the settings available here. 9.3.4 Frequency protection 9.3.4.1 Overview For Frequency protection there are settings for Underfrequency, Overfrequency and Rate of change of frequency.
  • Page 54: General Current And Voltage Protection Cvgapc

    Section 9 1MRK511251-UEN B Read and change settings available are based on the data from these inputs. Within each instance operation for the included functions can be set to On or Off and a large number of parameters can be set. 9.3.5.2 General current and voltage protection CVGAPC Main menu/Settings/Setting Group N/Multipurpose protection/...
  • Page 55: Event Counter Cntggio

    Section 9 1MRK511251-UEN B Read and change settings 9.3.7.2 Event counter CNTGGIO Main menu/Setting/Setting group N/Monitoring/EventCounter(GGIO)/ CNTGGIO:x Here the function can be set on or off. 9.3.7.3 Fault locator LMBRFLO Main menu/Settings/Setting group N/Monitoring/FaultLocator(RFLO)/ LMBRFLO:x/FLO1 Setting data entered here are the various measured or calculated impedances and resistances of the protected line section.
  • Page 56: Logicrsmemory

    Section 9 1MRK511251-UEN B Read and change settings 9.3.8.5 LogicRSMemory Main menu/Settings/Setting group N/Logic/LogicRSMemory/RSMEMORY:x Displays setting parameters for operating mode of memory function. 9.3.8.6 LogicSRMemory Main menu/Settings/Setting group N/Logic/LogicSRMemory/SRMEMORY:x Displays setting parameters for operating mode of memory function. 9.3.8.7 LogicTimerSet Main menu/Settings/Setting Group N/Logic/LogicTimerSet/TIMERSET:x Displays settable parameters for Operation (On or Off) and delay for settable timer.
  • Page 57: Section 10 Diagnose Ied Status

    Section 10 1MRK511251-UEN B Diagnose IED status Section 10 Diagnose IED status About this chapter This chapter describes where in the HMI tree to find the cause of an internal IED failure and information about the IED as such. 10.1 Read internal events Main menu/Diagnostics/Internal events Internal events in the diagnostics menu of the HMI tree shows a time stamped list...
  • Page 58 Section 10 1MRK511251-UEN B Diagnose IED status Displays various communication status signals for rear AB port communication. Main menu/ Diagnostics/Communication/Rear OEM - port CD Displays various communication status signals for rear CD port communication. Main menu/ Diagnostics/Communication/Redundant PRP Displays communication status for redundant station bus communication. Operator's manual...
  • Page 59: Section 11 Test The Ied

    Section 11 1MRK511251-UEN B Test the IED Section 11 Test the IED About this chapter This chapter describes the tests that can be performed in the test section of the HMI. 11.1 Overview The test part of the tree view in the HMI has a number of submenus for test and viewing activities.
  • Page 60: Ied Test Mode

    Section 11 1MRK511251-UEN B Test the IED individual function. One of the submenus shows the status of the LEDs on the HMI. 10. Communication displays submenus and Station communication. All measurement descriptions in this document reflect the maximum number of hardware units possible in any application.
  • Page 61: View Binary Output Values

    Section 11 1MRK511251-UEN B Test the IED 11.4 View binary output values 11.4.1 Overview Binary output values show the status of each individual output in the Binary output module (BOM). If the signal matrix tool is used binary outputs are depicted as virtual outputs.
  • Page 62: Frequency Protection

    Section 11 1MRK511251-UEN B Test the IED 11.5.4 Frequency protection Main menu/Test/Function test modes/Frequency protection Test of up to six instances of rate of change of frequency. 11.5.5 Multipurpose protection Main menu/Test/Function test modes/MultipurposeProtection Test of up to twelve instances of the general current and voltage function CVGAPC. 11.5.6 Secondary system protection Main menu/Test/Function test modes/Secondary system supervision...
  • Page 63: Four Step Directional Negative Phase Sequence Overcurrent Protection Ns4Ptoc

    Section 11 1MRK511251-UEN B Test the IED 11.6.1.1 Four step directional negative phase sequence overcurrent protection NS4PTOC Main menu/Test/Function status/Current protection/ NegSecOverCurr4Step(PTOC,46I2)/NS4PTOC:x Displays output data of NS4PTOC. 11.6.1.2 Four step phase overcurrent protection OC4PTOC Main menu/Test/Function status/Current protection/ PhaseOverCurrent4Step(PTOC,51_67)/OC4PTOC:x Displays available instances of OC4PTOC with several measurements per instance. These measurements are primarily trip and start signal indications from each phase and from the various steps in the protection scheme.
  • Page 64: Two Step Undervoltage Protection Uv2Ptuv

    Section 11 1MRK511251-UEN B Test the IED 11.6.2.2 Two step undervoltage protection UV2PTUV Main menu/Test/Function status/Voltage protection/ UnderVoltage2Step(PTUV, 27)/UV2PTUV:x Displays available instances of UV2PTUV with several measurements per instance. The measurement data includes operate signals and start signals. 11.6.3 Frequency protection The measurements generated by the Underfrequency, Overfrequency and Rate-of- change of frequency functions are available under the paths outlined below.
  • Page 65: General Current And Voltage Protection Cvgapc

    Section 11 1MRK511251-UEN B Test the IED 11.6.4.1 General current and voltage protection CVGAPC Main menu/Test/Function status/Multipurpose protection/ GeneralCurrentVoltage(GAPC)/CVGAPC:x Displays available instances of CVGAPC with a number of output quantities per instance. These include error signals from overcurrent functions, trip and start signals from overcurrent, undercurrent, overvoltage and undervoltage.
  • Page 66: Commands

    Section 11 1MRK511251-UEN B Test the IED 11.6.6.2 Commands In the commands menu it is possible to view three sets of values. These are found under the submenus menucascade/uicontrol. Automation bits, command function for DNP3.0 AutomationBits Main menu/Test/Function status/Control/Commands/Automation Bits/ AUTOBITS:x Displays the output data of the AutomationBits function.
  • Page 67: Logical Signal Status Report Binstatrep

    Section 11 1MRK511251-UEN B Test the IED 11.6.7.1 Logical signal status report BINSTATREP Main menu/Test/Function status/Monitoring/BinarySignalStatusReport/ BINSTATREP:x Displays sets of output measurements with several outputs per set of measurements. 11.6.7.2 Disturbance report DRPRDRE Test/Function status/Monitoring/DisturbanceReport(RDRE) Displays data about disturbance reports. The disturbance report can be switched off, a disturbance report that has been initiated is indicated by a boolean number, as are completed reports and cleared reports.
  • Page 68: Iec61850 Generic Communication I/O Functions 16 Inputs Sp16Ggio

    Section 11 1MRK511251-UEN B Test the IED Displays the number of satellites supplying positioning and timing data to the GPS module. 11.6.7.7 IEC61850 generic communication I/O functions 16 inputs SP16GGIO Main menu/Test/Function status/Monitoring/IndicationBits(GGIO)/ SP16GGIO:x Displays the output data of the SP16GGIO function. 11.6.7.8 LEDs Main menu/Test/Function status/Monitoring/LEDs/Start and trip LEDs...
  • Page 69: Integer To Boolean 16 Conversion Ib16Fcvb, Ib16

    Section 11 1MRK511251-UEN B Test the IED 11.6.8.2 Integer to Boolean 16 conversion IB16FCVB, IB16 Main menu/Test/Function status/Logic/IntToBool16(FCVB)/IB16FCVB:x Main menu/Test/Function status/Logic/IntToBool16/IB16:x Displays the output data of the IntToBool16 function. 11.6.8.3 Tripping logic SMPPTRC Main menu/Test/Function status/Logic/TripLogic(PTRC94)/SMPPTRC:x Displays available instances of the function SMPPTRC with some measurements per instance.
  • Page 70: Communication

    Section 11 1MRK511251-UEN B Test the IED Displays available instances of the function (TIMERSET). The output data type is boolean and indicates whether the output from the timer pickup is delayed (ON) or if the drop out (OFF) is delayed. 11.6.9 Communication 11.6.9.1...
  • Page 71: Setting Groups

    Section 11 1MRK511251-UEN B Test the IED 11.6.10 Setting groups Main menu/Test/Function status/Setting groups Displays available setting groups and indicates which of them is in use. 11.6.11 Test Main menu/Test/Function status/Test Displays the parameters ACTIVE, OUTPUT and SETTING. The ACTIVE parameter indicates whether the IED is in test mode or not, the OUPUT parameter indicates whether test mode has been activated by a binary input and the SETTING parameter indicates whether or not test mode has been activated by a setting.
  • Page 73: Section 12 Control And Supervise The Bay

    Section 12 1MRK511251-UEN B Control and supervise the bay Section 12 Control and supervise the bay About this chapter This chapter describes the various control and supervision functions available in the HMI. In particular, how the available on the display can be used for this purpose.
  • Page 74 Section 12 1MRK511251-UEN B Control and supervise the bay Symbol Description Autotransformer xx05000227.vsd IEC05000227 V1 EN Busbar xx05000228.vsd IEC05000229 V1 EN Capacitor xx05000231.vsd IEC05000231 V1 EN Circuit breaker xx05000232.vsd IEC05000232 V1 EN Damping Coil xx05000233.vsd IEC05000233 V1 EN Current Transformer xx05000234.vsd IEC05000234 V1 EN Earth...
  • Page 75: Control Screen Messages

    Section 12 1MRK511251-UEN B Control and supervise the bay Symbol Description Trafo 3 windings xx05000245.vsd IEC05000245 V1 EN Truck xx05000248.vsd IEC05000248 V1 EN VT 2 windings xx05000247.vsd IEC05000247 V1 EN 12.1.3 Control screen messages These messages appear at the bottom of the SLD screen and are in the form of a prompt asking the user to confirm an action, such as the opening of a circuit breaker.
  • Page 77: Section 13 Reset

    Section 13 1MRK511251-UEN B Reset Section 13 Reset About this chapter This chapter describes how to reset the IED and when this is necessary. 13.1 Reset guide for IED 13.1.1 Reset counters 13.1.1.1 Reset event counter CNTGGIO The event counter is reset under Reset counters in the HMI tree. Main menu/Reset/Reset counters/EventCounter(GGIO)/CNTGGIO:x 13.1.1.2 Reset pulse counter PCGGIO...
  • Page 78: Reset Leds

    Section 13 1MRK511251-UEN B Reset 13.1.3 Reset LEDs 13.1.3.1 Start and trip LEDs By activating this reset, the colored LEDs above the LCD, if they are latched, will be reset. Main menu/Reset/Reset LEDs/Start and trip LEDs In the dialog box that appears, choose YES to reset. 13.1.3.2 All indication LEDs Activating the Reset of indication LEDs will zero all fifteen LEDs to the right of...
  • Page 79: Section 14 Authorization

    Section 14 1MRK511251-UEN B Authorization Section 14 Authorization About this chapter This chapter describes password procedures and levels of access in the system. 14.1 Overview To safeguard the interests of our customers, both the IED and the tools that are accessing the IED are protected, by means of authorization handling.
  • Page 80 Section 14 1MRK511251-UEN B Authorization Table 2: Pre-defined user types Access rights System Protection Design User Guest Super User SPA Guest Operator Engineer Engineer Administrator Basic setting possibilities (change setting group, control settings, limit supervision) Advanced setting possibilities (for example protection settings) Basic control possibilities (process control, no bypass) Advanced control possibilities...
  • Page 81: Logon Or Logoff

    Section 14 1MRK511251-UEN B Authorization At least one user must be included in the UserAdministrator group to be able to write users, created in PCM600, to IED. 14.3 LogOn or logOff The Authorization menu allows the user to logOn and, logOff. The HMI path is as follows: Main menu/Authorization 14.4...
  • Page 82: Internet Protocol Ports Security Guideline

    Section 14 1MRK511251-UEN B Authorization 14.5 Internet Protocol ports security guideline The Internet Protocol ports security guide line can not suggest concrete products for a secure system setup. This must be decided along the specific project, requirements and existing infrastructure. The required external equipment can be separated devices or devices that combine firewall, router and secure VPN functionality.
  • Page 83 Section 14 1MRK511251-UEN B Authorization TCP (default port 20 000). It is defined in the configuration which type of Ethernet communication is used. Only one type is possible for a specific configuration. • The PCM600 port for SPA (port 7001) is used for configuration and parameter setting using the PCM600 tool and a proprietary protocol SPA and is fixed and can not be changed.
  • Page 85 Section 15 1MRK511251-UEN B Glossary Section 15 Glossary About this chapter This chapter contains a glossary with terms, acronyms and abbreviations used in ABB technical documentation. Alternating current Application configuration tool within PCM600 A/D converter Analog-to-digital converter ADBS Amplitude deadband supervision...
  • Page 86 Section 15 1MRK511251-UEN B Glossary Combined backplane module CCITT Consultative Committee for International Telegraph and Telephony. A United Nations-sponsored standards body within the International Telecommunications Union. CAN carrier module CCVT Capacitive Coupled Voltage Transformer Class C Protection Current Transformer class as per IEEE/ ANSI CMPPS Combined megapulses per second Communication Management tool in PCM600...
  • Page 87 Section 15 1MRK511251-UEN B Glossary Distributed Network Protocol as per IEEE Std 1815-2012 Disturbance recorder DRAM Dynamic random access memory Disturbance report handler Digital signal processor Direct transfer trip scheme EHV network Extra high voltage network Electronic Industries Association Electromagnetic compatibility (Electromotive force) Electromagnetic interference EnFP...
  • Page 88 Section 15 1MRK511251-UEN B Glossary Human-machine interface HSAR High speed autoreclosing High-voltage HVDC High-voltage direct current IDBS Integrating deadband supervision International Electrical Committee IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for protective current transformers for transient performance IEC 60870-5-103 Communication standard for protective equipment.
  • Page 89 Section 15 1MRK511251-UEN B Glossary IP 20 Ingression protection, according to IEC standard, level 20 IP 40 Ingression protection, according to IEC standard, level 40 IP 54 Ingression protection, according to IEC standard, level 54 Internal failure signal IRIG-B: InterRange Instrumentation Group Time code format B, standard 200 International Telecommunications Union Local area network...
  • Page 90 Section 15 1MRK511251-UEN B Glossary PCM600 Protection and control IED manager PC-MIP Mezzanine card standard PCI Mezzanine card Permissive overreach POTT Permissive overreach transfer trip Process bus Bus or LAN used at the process level, that is, in near proximity to the measured and/or controlled components Power supply module Parameter setting tool within PCM600 PT ratio...
  • Page 91 Section 15 1MRK511251-UEN B Glossary SNTP Simple network time protocol – is used to synchronize computer clocks on local area networks. This reduces the requirement to have accurate hardware clocks in every embedded system in a network. Each embedded node can instead synchronize with a remote clock, providing the required accuracy.
  • Page 92 Section 15 1MRK511251-UEN B Glossary UTC is derived from International Atomic Time (TAI) by the addition of a whole number of "leap seconds" to synchronize it with Universal Time 1 (UT1), thus allowing for the eccentricity of the Earth's orbit, the rotational axis tilt (23.5 degrees), but still showing the Earth's irregular rotation, on which UT1 is based.
  • Page 94 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...

Table of Contents