How to build the program

The programmer connects a function block to other blocks through a Block
Parameter Set. The sets are also used for reading values from the drive application
program and transferring data to the drive application program. Each Block
Parameter Set consists of five parameters.
The figure shows the use of Block
Parameter Set 1 in the ACS800
Standard Application Program
(parameters 84.05 to 84.09):
- Parameter 84.05 selects the
function block type.
- Parameter 84.06 selects the source
that input I1 of the function block is
connected to.
- Parameter 84.07 selects the source
that input I2 of the function block is
connected to.
- Parameter 84.08 selects the source
that input I3 of the function block is
connected to.
- Parameter 84.09 stores the value of
the function block output. The user
cannot edit the parameter value.
Adaptive Program
ACT. SIGNAL/
PARAMETER
TABLE
1.01
1.02
• • •
99.99
Block Parameter Set 1
Select
ADD
...
XOR
84.05
Select
84.06
Select
84.07
Select
84.08
Store
84.09
ADD
+
I1
I2
O
I3