The table below lists the parameters and parameters values that are essential for the
Adaptive Program. The abbreviation FbEq stands for fieldbus equivalent.
Index Parameter name /
value
10
START/STOP/DIR
10.01 EXT1 STRT/STP/DIR
PARAM 10.04
10.02 EXT2 STRT/STP/DIR
PARAM 10.05
10.04 EXT 1 STRT PTR
-255.255.31 ...
+255.255.31 / C.-32768
... C.32767
10.05 EXT 2 STRT PTR
-255.255.31 ...
+255.255.31 / C.-32768
... C.32767
11
REFERENCE SELECT Parameters through which the Adaptive Program can control the reference of
11.02 EXT1/EXT2 SELECT
PARAM 11.09
11.03 EXT REF1 SELECT
PARAM 11.10
11.06 EXT REF2 SELECT
PARAM 11.11
11.09 EXT 1/2 SEL PTR
-255.255.31 ...
+255.255.31 / C.-32768
... C.32767
11.10 EXT 1 REF PTR
-255.255.31 ...
+255.255.31 / C.-32768
... C.32767
11.11 EXT 2 REF PTR
-255.255.31 ...
+255.255.31 / C.-32768
... C.32767
14
RELAY OUTPUTS
14.01 RELAY RO1 OUTPUT
PARAM 14.16
14.02 RELAY RO2 OUTPUT
Actual signals and parameters in ACS800 Standard Application Program
Description
Parameters through which the Adaptive Program can control the start, stop
and direction of the drive.
Source selected by
10.04
Source selected by 10.05.
Selects the source for parameter 10.01.
Parameter pointer or constant value:
- Parameter pointer: Inversion, group, index and bit fields. The bit number is
effective only for blocks handling boolean inputs.
- Constant value: Inversion and constant fields. The inversion field must have
value C to enable the setting of the constant.
Selects the source for 10.02.
Parameter pointer or constant value. See Parameter
the drive.
Source selected by 11.09.
Source selected by 11.10.
Source selected by 11.11.
Selects the source for 11.02.
Parameter pointer or constant value. See Parameter
Selects the source for 11.03.
Parameter pointer or constant value. See Parameter
Selects the source for 11.06.
Parameter pointer or constant value. See Parameter
Parameters through which the Adaptive Program can control the relay
outputs of the drive.
Source selected by parameter 14.16.
10.04.
10.04.
10.04.
10.04.
FbEq
17
17
16
37
38
36