Repair And Replacement Parts - Whirlpool Gold WFD193 Installation Instructions Manual

93 percent convertible multispeed gas furnace
Hide thumbs Also See for Gold WFD193:
Table of Contents

Advertisement

To remove filters from an external filter rack in an upright upflow
installation, follow the directions provided with external filter rack
kit.
Horizontal Furnace Filter Removal
Filters in horizontal installations are located in the central return
register or the ductwork near the furnace.
To remove:
1. Disconnect power to the furnace.
2. Remove the filter(s) from the central return register or
ductwork.
3. Replace the filter(s) by reversing the procedure for removal.
4. Reconnect power to the furnace.
Media Air Filter or Electronic Air Cleaner Removal
Follow the manufacturer's directions for service.
Burners
Visually inspect the burner flames periodically during the heating
season. Turn on the furnace at the thermostat and allow several
minutes for flames to stabilize, since any dislodged dust will alter
the flames normal appearance. Flames should be stable, quiet,
soft, and blue (dust may cause orange tips but they must not be
yellow). They should extend directly outward from the burners
without curling, floating, or lifting off. Flames must not impinge on
the sides of the heat exchanger firing tubes.
Induced Draft and Circulator Blowers
The bearings in the induced draft blower and circulator blower
motors are permanently lubricated by the manufacturer. No
further lubrication is required. Check motor windings for
accumulation of dust which may cause overheating. Clean as
necessary.
Condensate Trap and Drain System (Qualified Servicer
Only)
Annually inspect the drain tubes, drain trap, and field-supplied
drain line for proper condensate drainage. Check drain system
for hose connection tightness, blockage, and leaks. Clean or
repair as necessary.
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or air supply can create a nearly
invisible coating on the flame sensor. This coating acts as an
insulator causing a drop in the flame sense signal. If the flame
sense signal drops too low the furnace will not sense flame and
will lock out. The flame sensor should be cleaned by a qualified
servicer using emery cloth or steel wool. Following cleaning, the
flame sense signal should be as indicated in the Specifications
Sheet.
Flue Passages (Qualified Servicer Only)
The heat exchanger flue passageways should be inspected at the
beginning of each heating season. If necessary, clean the
passageways as outlined below.
1. Disconnect power and turn off the gas supply to the furnace.
2. Disconnect the gas line and remove the burner/manifold
assembly by removing the screws securing the assembly to
the partition panel.
3. Disconnect the flue pipe system from the induced draft
blower.
4. Remove the induced draft blower and, drain and pressure tap
hoses from the recuperator coil front cover.
38
5. Remove the recuperator coil front cover to expose the coil
tubes and turbulators.
6. Remove the recuperator coil turbulators individually by slowly
pulling each turbulator forward firmly.
7. Clean the recuperator coil tubes using a long handle wire
brush, such as a gun cleaning brush.
8. Clean the primary heat exchanger tubes using a wire brush
attached to a length of high grade stainless steel cable, such
as drain cleanout cable. Attach a variable speed reversible
drill to the other end of the cable. Slowly rotate the cable with
the drill and insert it into one of the heat exchanger tubes.
While reversing the drill, work the cable in and out several
times to obtain sufficient cleaning. Repeat for each tube.
9. Clean the residue from the furnace by using a vacuum
cleaner.
10. Replace the parts removed in the previous steps in reverse
order.
11. Turn on electrical power and gas to furnace. Check for leaks
and proper furnace operation.
12. Severe heat exchanger fouling is an indication of an
operational problem. Perform the checks listed in "Start-up
Procedure and Adjustments" to reduce the chances of
repeated fouling.
Bottom Return Removal
1. Disconnect power to the furnace.
2. Remove blower compartment door.
3. Push back and up on the wire filter retainer to release it from
under the front lip of the furnace base pan.
4. Slide the filter forward and out.
5. Replace the filter by reversing the procedure.

Repair and Replacement Parts

When ordering any of the listed functional parts, be sure to
provide the furnace model, manufacturing, and serial numbers
with the order.
Although only functional parts are shown in the parts list, all sheet
metal parts, doors, etc., may be ordered by description.
Parts are available from your distributor.
Functional Parts List
Gas Control Valve
Gas Manifold
Natural Gas Orifice
Propane Gas Orifice
Igniter
Rollout Limit Switch
Primary Limit Switch
Auxiliary Limit Switch
Pressure Switch
Induced Draft Blower
Capacitor
Flame Sensor
Blower Motor
Blower Wheel
Blower Mounting Bracket
Blower Cutoff
Blower Housing
Heat Exchanger
Recuperator Coil
Coil Front Cover
Integrated Control Module
Transformer
Door Switch

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gold wpio-299f

Table of Contents