P R O D U C T G U I D E
RER620
Advanced recloser protection & control

Advertisement

Table of Contents
loading

Summary of Contents for ABB RER620

  • Page 1 — P R O D U C T G U I D E RER620 Advanced recloser protection & control...
  • Page 2: Table Of Contents

    006–007 3. Protection functions Control functions 008–011 4. Application 031–032 Condition monitoring functions 012–013 5. Supported ABB solutions 21. Display 6. Control 22. Local HMI 7. Measurements 23. Mounting methods 8. Digital fault recorder 24. Protection and control relay case and drawout 9.
  • Page 3: Description

    • Field data from recloser control, Sequence of tion. RER620 is a member of ABB’s Relion® family Events, digital waveform recording, advanced and a part of its 620 protection and control prod- metering, setting etc.
  • Page 4: Standard Configurations

    Ethernet communications included standard with 2. Standard configurations parallel support of DNP3.0 Level 2+*, IEC 60870-5- The RER620 relay’s main application is feeder pro- 104, Modbus and IEC61850 and SNTP over TCP/IP. tection and control and offers one standard config-...
  • Page 5 Other functions Uninterruptable Power Supply (UPS) including: battery charger, heater control, auxiliary power for external modems, voltage boost • Universal Power Driver (UPD) for ABB GridShield series of reclosers and others • Programmable buttons (16 buttons) • Move function block (8 outputs) •...
  • Page 6: Protection Functions

    Up/Down counters UDFCNT1...UDFCNT12 (12 counters) • 1) Three phase tripping is always enabled when ordering RER620. Single phase tripping is optional 2) Voltages connected to X[130] terminals 1 - 9 are considered as Source 1 3) Voltages connected to X[130] terminals 11 - 18 are considered as Source 2 4) Polarizing voltage is taken from X[130] terminals 1 - 9 5) UPS is mandatory when using RER620 with either ABB Gridshield or G&W Viper recloser...
  • Page 7 Io selectable by setting, Io calculated as default Under-frequcny and df /dt based load shedding function In the case of ABB GridShield recloser , these are embedded Capacitor Voltage Divider (CVD) with 10,000:1 ratio In the case of ABB GridShield recloser , these are embedded Current Transformer...
  • Page 8: Application

    (because of transformer inrush currents is used by other time overcurrent and in- current), RER620 have built in logic to detect ener- stantaneous ground protective elements. When ap- gization and consequently make necessary action plicable, the core-balance current transformers can such as desensitize or block protective elements.
  • Page 9 Figure 2. Peer-to-peer relay Fault Detection Isolation and Resto- ration (FDIR) con- trol using IEC61850 GOOSE messaging IEC 61850 IEC 61850 (GridShield ) (GridShield ) Fault Fault (GridShield ) (GridShield ) (GridShield ) (GridShield )
  • Page 10 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L Figure 3. Recloser appli- cation with Distributed Energy Resources (DER) (GridShield )
  • Page 11 Figure 4. Recloser Loop Control Midpoint Sectionalizing Recloser Recloser Substation Circuit Breaker (GridShield ) (GridShield ) Source 1 3 VT’s 1 VT 1 VT Tie Point Recloser (GridShield ) Sectionalizing Midpoint 3 VT’s Recloser Recloser Substation Circuit Breaker (GridShield ) (GridShield Source 2 Normally Closed...
  • Page 12: Supported Abb Solutions

    R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L 5. Supported ABB solutions ues. Better understanding of the process behavior ABB’s 620 series protection and control relays to- by joining time-based process measurements with gether with the COM600 Station Automation de-...
  • Page 13 Wireless (radio, Note 1: Peer-to-peer over IEC61850 - GOOSE can be used LAN/WAN cellular...) for sharing information between recloser for possible RER620 restoration, interlocking, isolation etc... Wireless Note 2: DNP3.0 (Serial or TCP/IP), IEC 60870-5-101, IEC modem 60870-5-104 supported Wireless...
  • Page 14: Control

    R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L 6. Control channels can be set to start a recording on the ris- The protection and control relay offers status and ing or the falling edge of the binary signal or both.
  • Page 15: Recloser/Circuit Breaker Condition Monitoring

    UPS can draw power from the battery the recloser/circuit breaker reduces due to wear- and make it available to the RER620, as well any ing. The wearing in the recloser/breaker depends other auxiliary devices, in the event the main power on the tripping current, and the remaining life of source is lost.
  • Page 16: Universal Power Driver (Upd)

    The binary input turn-on thresholds the need to disconnect communication connec- are programmable from 18…176 V DC by adjusting tions. the relay’s parameter settings. Besides the dedi- cated trip/close outputs that are mandatory to drive the magnetic actuators in reclosers, RER620...
  • Page 17 The relay can be connected to an Ethernet-based ported for DNP3. RER620 listens the DNP master on communications network via a copper RJ45 both channels - serial and TCP/IP - simultaneously (100Base TX) or fiber optic LC (100Base FX) con- and responds on both ports.
  • Page 18 10.5 lbs (4.8 kg) Weight unit only 6.0 lbs (2.8 kg) — Table 6. Power supply (RER620) Description Type 2 V nominal (V 60 V DC variation 50 to 120% of V (30 to 72 V DC) Start-up threshold 48 V DC (60 V DC ×...
  • Page 19 — Table 8. Energizing inputs Description Value Rated frequency 50/60 Hz ± 5 Hz Current inputs Rated current, I 0.2/1 A 1/5 A Thermal withstand capability: - Continuously 20 A - For 1 s 100 A 500 A Dynamic current withstand: - Half-wave value 250 A 1250 A...
  • Page 20 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L — Table 12. Single-pole power output relays Description Value Rated voltage...
  • Page 21 Storage test +85°C 96h -40°C 96h *Unless otherwise specified, tests are applicable to both RER620 and UPS. For protection and control relays with an LC communication interface, the maximum operating temperature +70°C. LCD may be unreadable, but protection and control relay is operational.
  • Page 22 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L Protection functions — Table 23.
  • Page 23 — Table 24. 67/51P and 67/50P technical data Description Value Depending on the frequency of the current measured: f ±2Hz Current: ±1.5% of the set value or ±0.002 x I Voltage: ±1.5% of the set value or ±0.002 x U Phase angle: 67/51P, 67/50P-1 ±2°...
  • Page 24 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L — Table 26. 67/51N and 67/50N technical data Description Value Depending on the frequency of the current measured: f...
  • Page 25 — Table 28. 46PD technical data Characteristic Value Depending on the frequency of the current measured: f ±2Hz Operation accuracy ±2% of the set value Pickup time < 70 ms Reset time < 40 ms Reset ratio Typical 0.96 Retardation time <...
  • Page 26 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L — Table 31. 27 technical data Characterstic Value Depending on the frequency of the current measured: f...
  • Page 27 — Table 34. FRPFRQ technical data Characteristic Value f< ±10 mHz Operation accuracy ±100 mHz/s (in range |df/dt| < 5 Hz/s) df/dt ±2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s) f>/f< < 80 ms Start time df/dt <...
  • Page 28 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L Protection functions — Table 37.
  • Page 29 — Table 42. V1, V2, V0 technical data Characteristic Value Depending on the frequency of the current measured: f/f = ±2Hz At voltages in range 0.01 to 4.00 x I Operation accuracy ±1.0% or ±0.002 x V Suppression of harmonics DFT: -50dB at f = n x f , where n = 2, 3, 4, 5,…...
  • Page 30 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L Control functions — Table 45.
  • Page 31 Condition monitoring functions — Table 47. 52CM technical data Characteristic Value ±1.5% or ±0.002 x I (at currents in the range of 0.1 to 10 x I Current measuring accuracy ±5.0% (at currents in the range of 0.1 to 40 x I Operate time accuracy ±1.0% of the set value or ±20 ms Travelling time measurement...
  • Page 32 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L — Table 50. 59PS technical data Characteristic Value Depending on the frequency of the current measured: f...
  • Page 33: Display

    21. Display — Table 53. Large display The relay’s local HMI includes a large LCD screen as a standard. The large LCD display offers full front- Character size Rows in the view Characters per row panel user-interface functionality with menu navi- Large, variable gation and menu views.
  • Page 34: Local Hmi

    These pushbuttons are accessible in the RER620 for mak- ing any user defined logic. For each push button different operation modes such as pulsed, toggled are available.
  • Page 35: Mounting Methods

    23. Mounting methods 24. protection and control relay case and drawout The RER620 can be installed as flush mounted. Fur- unit ther, the relays can be mounted in any standard 19" For safety reasons, the protection and control relay instrument cabinet by means of 19” mounting pan- cases are provided with automatically operating els available with cut-outs for one or two relays.
  • Page 36: Selection And Ordering Data

    R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L 25. Selection and ordering data Use the ordering key information to generate the The relay type and serial number label identifies the order number when ordering complete protection...
  • Page 37: Accessories And Ordering Data

    Table 55. Tools Item Order number PCM600 2.6 FP1 or later Web-browser based user interface IE 9.0 or later RER620 Connectivity Package 1.2 or later COM600 substation product 3.5 or later MicroSCADA Pro Substation Automation system 9.3.2 HF2 or later...
  • Page 38 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L — Table 56. Supported functions PCM Engineering Function WebHMI...
  • Page 39: Terminal Diagrams

    28. Terminal diagrams RER620 X100 X120 BI 1 Figure 9. RER620 standard configura- BI 2 IED FAILURE ALARM tion A with options BI 3 BI 4 IA (From OVR 3) IB (From OVR 3) IC (From OVR 3 ) X105...
  • Page 40: Certificates

    Reference manual, installation manual, You will find the latest relevant information on the operators manual, etc. The selection tool on the RER620 protection relay on the product page. web page helps you find the documents by the doc- ument category and language.
  • Page 41 Function name Configuration IEC61850 IEC60617 ANSI/C37.2 Description RA01 and RA02 Voltage protection SPHPTOV1 3U >(1) 59-1 Three-phase overvoltage 1, source 1 low stage SPHPTOV2 3U >(2) 59-2 Three-phase overvoltage 2, source 1 high stage SPHPTOV3 3U >(3) 59-3 Three-phase overvoltage 3, source 2 low stage SPHPTUV1 3U <(1) 27-1...
  • Page 42 R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L Function name Configuration IEC61850 IEC60617 ANSI/C37.2 Description...
  • Page 43: Document Revision History

    32. Document revision history — Table 58. Document revision history Revision & date Version Update A / December 2010 V1.1 Initial product version release B / November 2011 V1.1 PG&E Protocol, counters added C / August 2014 V1.2 Ability to read low currents added D/ July 2017 V1.2 Updated ordering aid...
  • Page 44 Coral Springs, FL 33065 Phone: +1 954 752 6700 Toll free: +1 800 523 2620 Product support: +1 954 825 0606 Toll free: +1 800 222 1946 abb.com/mediumvoltage abb.com/substationautomation © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.