Phasing - Siemens S7-1200 System Manual

Hide thumbs Also See for S7-1200:
Table of Contents

Advertisement

Technology instructions
9.3 Motion control
P = Pulse
D = Direction
2 - 20
PTO4
KHz (all
with
direction
output)
Ex. 3:
PTO1
4 - 200
PTO2
KHz (no
PTO3
direction
PTO4
output)
Ex. 4:
PTO1
P
2 - 100
PTO2
KHz;
PTO3
2 - 200
PTO4
KHz (all
with
direction
output)
9.3.1

Phasing

You have four options for the "Phasing" interface to the stepper/servo drive. These options
are as follows:
● PTO (pulse A and direction B): If you select a PTO (pulse A and direction B) option, then
one output (P0) controls the pulsing and one output (P1) controls the direction. P1 is high
(active) if pulsing is in the positive direction. P1 is low (inactive) if pulsing is in the
negative direction:
● PTO (count up A and count down B): If you select a PTO (count up A and count down B)
option, then one output (P0) pulses for positive directions and a different output (P1)
pulses for negative directions:
446
CPU on-board outputs
D
P
D
High-speed SB outputs Low-speed
P
D
System Manual, 03/2014, A5E02486680-AG
SB outputs
P
P
P
P
P
D
P
D
S7-1200 Programmable controller

Advertisement

Table of Contents
loading

Table of Contents