Siemens S7-1200 System Manual page 942

Hide thumbs Also See for S7-1200:
Table of Contents

Advertisement

Technical specifications
A.11 Digital signal boards (SBs)
Table A- 198 Wiring diagrams for the 200 kHz digital input/output SBs
SB 1223 DI 2 x 24 VDC/DQ 2 x 24 VDC,
200 kHz (6ES7 223-3BD30-0XB0)
Supports sourcing inputs only
For sourcing outputs, connect "Load" to "-" (shown). For sinking outputs, connect "Load" to "+".
and sourcing configurations are supported by the same circuitry, the active state of a sourcing load is opposite that of a
sinking load. A source output exhibits positive logic (Q bit and LED are ON when the load has current flow), while a sink
output exhibits negative logic (Q bit and LED are OFF when the load has current flow). If the module is plugged in with
no user program, the default for this module is 0 V, which means that a sinking load will be turned ON.
Table A- 199 Connector pin locations for SB 1223 DI 2 x 24 VDC/DQ 2 x 24 VDC, 200 kHz (6ES7
942
223-3BD30-0XB0)
Pin
X19
1
L+ / 24 VDC
2
M / 24 VDC
3
DI e.0
4
DI e.1
5
DQ e.0
6
DQ e.1
SB 1223 DI 2 x 5 VDC / DQ 2 x 5 VDC,
200 kHz (6ES7 223-3AD30-0XB0)
System Manual, 03/2014, A5E02486680-AG
Because both sinking
1
S7-1200 Programmable controller

Advertisement

Table of Contents
loading

Table of Contents