Digital Inputs And Outputs - Siemens S7-1200 System Manual

Hide thumbs Also See for S7-1200:
Table of Contents

Advertisement

A.5.3

Digital inputs and outputs

Table A- 73
Digital inputs
Technical data
Number of inputs
Type
Rated voltage
Continuous permissible voltage
Surge voltage
Logic 1 signal (min.)
Logic 0 signal (max.)
Isolation (field side to logic)
Isolation groups
Filter times
HSC clock input rates (max.)
(Logic 1 Level = 15 to 26 VDC)
Number of inputs on simultaneously
Cable length (meters)
Table A- 74
Digital outputs
Technical data
Number of outputs
Type
Voltage range
Logic 1 signal at max. current
Logic 0 signal with 10 KΩ load
Current (max.)
Lamp load
ON state resistance
Leakage current per point
Surge current
Overload protection
Isolation (field side to logic)
Isolation resistance
Isolation between open contacts
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
CPU 1215C
AC/DC/Relay
14
Sink/Source (IEC Type 1 sink)
24 VDC at 4 mA, nominal
30 VDC, max.
35 VDC for 0.5 sec.
15 VDC at 2.5 mA
5 VDC at 1 mA
500 VAC for 1 minute
1
us settings: 0.1, 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 10.0, 12.8, 20.0
ms settings: 0.05, 0.1, 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 10.0, 12.8, 20.0
100/80 kHz (Ia.0 to Ia.5)
30/20 kHz (Ia.6 to Ib.5)
7 (no adjacent points) at 60 °C horizontal or 50 °C vertical
14 at 55 °C horizontal or 45 °C vertical
500 m shielded, 300 m unshielded, 50 m shielded for HSC inputs
CPU 1215C AC/DC/Relay
and CPU 1215C DC/DC/Relay
10
Relay, dry contact
5 to 30 VDC or 5 to 250 VAC
--
--
2.0 A
30 W DC / 200 W AC
0.2 Ω max. when new
--
7 A with contacts closed
No
1500 VAC for 1 minute (coil to contact)
None (coil to logic)
100 MΩ min. when new
750 VAC for 1 minute
CPU 1215C
DC/DC/Relay
CPU 1215C DC/DC/DC
10
Solid state - MOSFET (sourcing)
20.4 to 28.8 VDC
20 VDC min.
0.1 VDC max.
0.5 A
5 W
0.6 Ω max.
10 μA max.
8 A for 100 ms max.
No
500 VAC for 1 minute
--
--
Technical specifications
A.5 CPU 1215C
CPU 1215C
DC/DC/DC
871

Advertisement

Table of Contents
loading

Table of Contents