Connecting Wires To Push-In Type Connectors; Connecting Protective Earthing; Connecting Protective Earthing To Relay - ABB RELION REX640 Installation Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759115 A
5.2.3
5.3
5.3.1
REX640
Installation Manual
Table 4:
Wire specifications for ring-lug type connectors
Connector type Wire size
Stranded
(mm²)
CT/VT
0.5...6
connectors
Signal
3)
0.13...3.3
connectors
1) Depends on the cable lug
2) Recommended ring lug connectors: C-RCI 1.5/M4 3240018, C-RCI 2.5/M4 3240023 and C-RCI 6/M4
3240027
3) For two wires 2x(0.2...1.5) mm2
4) Insulated ring lug M3, max outside diameter 8 mm

Connecting wires to push-in type connectors

Terminal blocks of push-in type are used for electrical connections.
1.
Connect the wire in one of the alternative ways.
When using stranded wire without ferrule, push the connector's release
button while inserting the wire.
When using wire with end ferrule, insert the wire without pushing the
release button.
Table 5:
Wire specifications for push-in type connectors
Connector type
Wire size
Stranded
(mm²)
Signal
0.2...2.5
connectors

Connecting protective earthing

Connecting protective earthing to relay

Connect the protection relay to earth using a 16.0 mm
lead of maximum 1.5 m. Extra length is required for door mounting.
1.
Using a TX30 screwdriver, loosen the protective earth screw to connect a
separate earth protection lead.
Stripping length
Crimp ferrule
(mm)
(mm²)
-
1)2)
-
1)4)
Stripping
Crimp ferrule
length
(mm)
(mm²)
0.2...2.5
10
Section 5
Connecting
Contact screw
Anchoring
tightening
screw tightening
torque (Nm)
torque (Nm)
1.2...1.5
1.2
1.13
0.35
Contact screw
Anchoring screw
tightening torque
tightening torque
(Nm)
(Nm)
-
0.2
2
flat copper cable. Use an earth
59