Autosynchronizer Application - ABB REX640 Product Manual

Hide thumbs Also See for REX640:
Table of Contents

Advertisement

REX640
Product version: 1
9 voltage channels to be freely allocated for the relay
functionalities. The stator winding temperatures are monitored
REX640
2 x AIM2 | CT: 12, VT: 8
U
Protection
APP12
Inst.
ANSI
1x
25AUTOSYNC
3x
25AUTOSYNCBT/T
3U
Generator 1
GUID-6D58C7F7-C41B-405E-B8F5-F6BDA25A6927 V1 EN
Figure 10.

Autosynchronizer application

In addition to conventional protection, control, measurement
and supervision duties, REX640 can perform both generator
(APP11) and non-generator (APP12) circuit breaker
synchronizing. Successful synchronization of two alternating
power sources can be done by matching their voltage,
frequency, phase sequence and phase angle. The circuit
breaker (CB) connects the two sources after a period of CB
closing time from the instant of a given close command. Hence,
all the conditions of synchronization need to be met at the
instant of CB close operation for successful synchronization.
Each REX640, being part of the overall synchronizing scheme,
contains its own synchronizer function. When a generator CB is
to be synchronized, the related REX640 controls the
generator's voltage, frequency and angle difference by
ABB
IEC 61850-8-1 GOOSE (signal interfacing between relays for synchronizing purposes)
LHMI
IEC
AUTOSYNC
AUTOSYNCBT/T
3U
U
REX640
2 x AIM2 | CT: 12, VT: 8
Protection
APP11
Inst.
ANSI
IEC
1x
25AUTOSYNC
AUTOSYNC
1x
25AUTOSYNCG
AUTOSYNCG
f
U
AVR
Governor
via the temperature sensors in the motor. These sensors are
connected to the RTD card within the relay.
LHMI
REX640
2 x AIM2 | CT: 12, VT: 8
Protection
APP12
Inst.
ANSI
IEC
1x
25AUTOSYNC
AUTOSYNC
3x
25AUTOSYNCBT/T
AUTOSYNCCBT/T
3U
3U
LHMI
requesting the generator's AVR and prime mover's governor to
change the set-points accordingly. The generator circuit
breaker synchronizing does not require information exchange
between other REX640 relays within the scheme.
When a non-generator CB is to be synchronized, all the REX640
relays within the scheme exchange information between
themselves in order to identify suitable generator(s) for the
voltage and frequency matching. Once the generators are
identified and selected, the REX640 related to the circuit
breaker to be synchronized sends a request to the selected
generator(s) REX640 for the required voltage and frequency
corrections. When the voltage, frequency and the angle
difference across the CB under synchronization are within the
set limits, REX640 closes the circuit breaker. The information
1MRS759144 A
LHMI
REX640
2 x AIM2 | CT: 12, VT: 8
U
Protection
APP12
Inst.
ANSI
IEC
1x
25AUTOSYNC
AUTOSYNC
3x
25AUTOSYNCBT/T
AUTOSYNCCBT/T
3U
LHMI
U
REX640
2 x AIM2 | CT: 12, VT: 8
Protection
APP11
Inst.
ANSI
1x
25AUTOSYNC
1x
25AUTOSYNCG
3U
U
AVR
Governor
Generator 2
IEC
AUTOSYNC
AUTOSYNCG
f
13