Distance Protection (Dstpdis) Main Settings - ABB REX640 Product Manual

Hide thumbs Also See for REX640:
Table of Contents

Advertisement

REX640
Product version: 1
Table 36. Distance protection (DSTPDIS) main settings
Parameter
Phase Sel mode GFC
EF detection Mod GFC
Operate delay GFC
Z Chr Mod Ph Sel GFC
Directional mode Zn1
R1 zone 1
X1 zone 1
X1 reverse zone 1
Z1 zone 1
Z1 angle zone 1
Z1 reverse zone 1
PP operate delay Zn1
R0 zone 1
X0 zone 1
Factor K0 zone 1
Factor K0 angle Zn1
Gnd operate Dl Zn1
Directional mode Zn2
R1 zone 2
X1 zone 2
X1 reverse zone 2
Z1 zone 2
Z1 angle zone 2
Z1 reverse zone 2
PP Op delay Mod Zn2
R0 zone 2
X0 zone 2
Factor K0 zone 2
Factor K0 angle Zn2
Gnd operate Dl Zn2
38
Function
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
DSTPDIS
Value (Range)
1 = Overcurrent
2 = Vol Dep Overcur
3 = Under impedance
4 = OC AND Und impedance
1 = Io
2 = Io OR Uo
3 = Io AND Uo
4 = Io AND IoRef
100...60000 ms
1 = Quadrilateral
2 = Mho (circular)
2 = Forward
3 = Reverse
1 = Non-directional
0.00...3000.00 Ω
0.00...3000.00 Ω
0.00...3000.00 Ω
0.01...3000.00 Ω
15.0...90.0°
0.00...3000.00 Ω
20...60000 ms
0.00...3000.00 Ω
0.00...3000.00 Ω
0.0...4.0
-135...135°
20...60000 ms
1 = Non-directional
2 = Forward
3 = Reverse
0.00...3000.00 Ω
0.00...3000.00 Ω
0.00...3000.00 Ω
0.01...3000.00 Ω
15.0...90.0°
0.00...3000.00 Ω
20...60000 ms
0.00...3000.00 Ω
0.00...3000.00 Ω
0.0...4.0
-135...135°
20...60000 ms
1MRS759144 A
Step
-
-
10
-
-
0.01
0.01
0.01
0.01
0.1
0.01
1
0.01
0.01
0.1
1
1
-
0.01
0.01
0.01
0.01
0.1
0.01
1
0.01
0.01
0.1
1
1