Table 30. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
Table 31. Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
Storage test
1)
For relays with an LC communication interface the maximum operating temperature is +70
Table 32. Product safety
Description
LV directive
Standard
Table 33. EMC compliance
Description
EMC directive
Standard
Table 34. RoHS compliance
Description
Complies with RoHS Directive 2011/65/EU
36
Requirement
Class 2
Class 2
Class 2
Type test value
• 96 h at +55ºC
• 16 h at +85ºC
1)
• 96 h at -25ºC
• 16 h at -40ºC
• 6 cycles (12 h + 12 h) at +25°C...+55°C,
humidity >93%
• 5 cycles (3 h + 3 h)
at -25°C...+55°C
• 96 h at -40ºC
• 96 h at +85ºC
o
C
Reference
2006/95/EC
EN 60255-27 (2014)
EN 60255-1 (2009)
Reference
2004/108/EC
EN 60255-26 (2013)
1MRS759144 A
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
Reference
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
IEC60068-2-14
IEC 60068-2-1
IEC 60068-2-2
ABB