15. Protection functions

Table 12. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Operation accuracy
Start time
3, 4
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Table 13. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Start value
Time multiplier
Operate delay time
Operating curve type
6
Table 14. Three-phase directional overcurrent protection (DPHxPDOC)
Characteristic
Operation accuracy
Start time
7, 8
Reset time
3 Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
4 Includes the delay of the signal output contact
5 Includes the delay of the heavy-duty output contact
6 For further reference, see the Operation characteristics table
7 Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
8 Includes the delay of the signal output contact
ABB
Value
PHLPTOC
Depending on the frequency of the measured current: fn
±2 Hz
±1.5% of the set value or ±0.002 × In
PHHPTOC and
±1.5% of set value or ±0.002 × In (at currents in the range of 0.1...10 × In)
PHIPTOC
±5.0% of the set value (at currents in the range of 10...40 × In)
PHIPTOC:
Minimum
IFault = 2 × set
16 ms
Start value
11 ms
IFault = 10 × set
Start value
PHHPTOC and
23 ms
PHLPTOC:
IFault = 2 × set
Start value
Typically 40 ms
Typically 0.96
<30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
Function
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC and
PHHPTOC
PHLPTOC and
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHIPTOC
Value
EFLPTOC
Depending on the frequency of the measured current: fn
±2 Hz
±1.5% of the set value or ±0.002 × In
EFHPTOC and
±1.5% of set value or ±0.002 × In (at currents in the range of 0.1...10 × In)
EFIPTOC
±5.0% of the set value (at currents in the range of 10...40 × In)
EFIPTOC:
Minimum
IFault = 2 × set Start value
16 ms
IFault = 10 × set Start value
11 ms
EFHPTOC and EFLPTOC:
23 ms
IFault = 2 × set Start value
Typically 40 ms
Typical
19 ms
12 ms
26 ms
5
Value (Range)
0.05...5.00 × In
0.10...40.00 × In
1.00...40.00 × In
0.05...15.00
40...200000 ms
40...200000 ms
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Definite time
Typical
19 ms
12 ms
26 ms
1MRS758725
Maximum
23 ms
14 ms
29 ms
Step
0.01
0.01
0.01
0.01
10
10
Maximum
23 ms
14 ms
29 ms
11