Figure 3. Parallel redundancy protocol (PRP) solution
The device can be connected to Ethernet-based communication
systems via the RJ-45 connector (100Base-TX) or the fiber optic
LC connector (1000Base-SX), depending on the product variant.
The device supports the following high accuracy time synchro-
nization method with a timestamping resolution of 4 μs required
especially in process bus applications.
PTP (IEEE 1588) v2 with Power Profile
IEEE 1588 v2 features
Ordinary Clock with Best Master Clock algorithm
One-step Transparent Clock for Ethernet ring topology
1588 v2 Power Profile
Receive (slave): 1-step/2-step
Transmit (master): 1-step
Layer 2 mapping
Peer to peer delay calculation
Multicast operation
Required accuracy of grandmaster clock is +/-1 μs.
8