FUNCTION OVERVIEW

4.1.1 Input from master module to inverter

(1) Operation command
The following items can be output any time from the master module to
the inverter as operation commands. (Refer to pages 39, 46)
FR-A500/F500 series
Operation Command
Terminal
Forward rotation command
STF
(STF)
Reverse rotation command
STR
(STR)
High speed operation
RH
command (RH) *1
Middle speed operation
RM
command (RM) *1
Low speed operation
RL
command (RL) *1
Jog operation selection (JOG)
JOG
*1
Second function selection
RT
(RT) *1
Current input selection (AU)
AU
*1
Instantaneous power failure
CS
restart selection (CS) *1
MRS
Output stop (MRS)
*1 These are factory-set signals. Input signals can be changed by input
terminal function selection (Pr. 180 and higher). Note that some signals do
not accept a command from the master module according to the settings.
Refer to page 15 for details. Signals to be assigned to input terminal
function selection (Pr. 180 and higher) differ according to the inverters. For
details, refer to the inverter manual.
*2 Signals can be assigned using input terminal function selection (Pr. 400 to
Pr. 402). Refer to page 8. (when the FR-A5NPA is connected)
(2) Set frequency/set speed
Write a setting change from the master module to the inverter. (Refer
to pages 38, 45.)
(3) Parameter write
You can write a function from the master module. Note that writing a
function during inverter operation will result in a write mode error. (Refer
to pages 35, 42.) Refer to the inverter manual for parameter details.
(4) Inverter reset
You can reset the inverter or reset an inverter error. (Refer to pages
37, 44, 50, 60.)
(Signal)
26
FR-V500 series
Operation Command
Terminal
Forward rotation command
STF
(STF)
Reverse rotation command
STR
(STR)
Low speed operation
DI1
command (RL) *1
Middle speed operation
DI2
command (RM) *1
High speed operation
DI3
command (RH) *1
Second function selection
DI4
(RT) *1
DI11
DI12
DI13
MRS
Output stop (MRS)
(Signal)
— *2
— *2
— *2