X500/X501 Drive-Cliq Interfaces; X520 Digital Inputs - Siemens SINAMICS Equipment Manual

Medium-voltage drives, supplementary component descriptions
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

5.2.2.2

X500/X501 DRIVE-CLiQ interfaces

Table 5-10
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
5.2.2.3

X520 digital inputs

Table 5-11
Type: Screw terminal 1
DI: Digital input; M: Electronics ground; M1: reference potential
1)
Supplementary component descriptions
Manual, 06/2019
X500/X501 DRIVE-CLiQ interfaces
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
X520: Digital inputs
Terminal
Designation
1
DI 0
2
DI 1
3
DI 2
4
DI 3
5
M1
6
M
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
Technical data
1)
Voltage: -3 ... +30 V
Electrical isolation: Yes
Reference potential: M1
Input characteristic acc. to IEC 61131-2, type 1
Input voltage (including ripple)
"1" signal: 15 ... 30 V
"0" signal: -3 ... +5 V
Input current
at 24 V DC: typ. 9 mA
at <0.5 mA: Signal "0" reliably detected
Input delay
for "0" → "1": typ. 50 µs max. 100 µs
For "1" → "0": typ. 130 µs/max. 150 µs
Terminal Modules