Behavior Of The Leds In The Operating State - Siemens SINAMICS Equipment Manual

Medium-voltage drives, supplementary component descriptions
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

3.1.3.3

Behavior of the LEDs in the operating state

Table 3-14
Control Unit CU320-2 PN – Description of the LEDs during operation
LED
Color
RDY
(READY)
Green
Red
Red/
green
Orange
Green/
orange
or
red/
orange
Supplementary component descriptions
Manual, 06/2019
Status
Description, cause
Off
Electronics power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Flashing
Commissioning/reset
light
0.5 Hz
Flashing
Writing to the memory card
light
2 Hz
Flashing
PROFIenergy energy saving mode is active
light
For more detailed information see Function Manual
0.5 s on
"SINAMICS S120 Drive Functions".
3 s off
Flashing
General error
light
2 Hz
Flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz
Flashing
Updating the firmware of the DRIVE-CLiQ compo‐
light
nents
0.5 Hz
Flashing
DRIVE-CLiQ component firmware update com‐
light
plete. Wait for POWER ON for the components in
2 Hz
question.
Flashing
Component recognition by flashing DCP
light
Remark:
1 Hz
Both options depend on the LED status when com‐
ponent recognition is activated via DCP.
Flashing
Component recognition via LED is activated
light
(p0124[0]=1).
2 Hz
Remark:
Both options depend on the LED status when com‐
ponent recognition is activated via p0124[0] → 1.
3.1 Control Unit CU320-2 PN (PROFINET)
Remedy
Check power supply
Check parameterization / con‐
figuration
Obtain licenses
Turn POWER ON for the com‐
ponents in question
1)
Control Units