5.3.2.4

X531-X536 temperature sensor inputs

Table 5-25
X531-X536: Temperature sensor inputs
Terminal
1
2
3
4
Type: Spring-loaded terminal 3
Measuring current via temperature sensor connection: approx. 0.83 mA
When connecting temperature sensors with 3 wires, a jumper must be inserted between
X53☐.2 and X53☐.4 (☐ = 1...6).
Table 5-26
Terminal
X531
X532
X533
X534
X535
X536
NOTICE
Damage to motor in the event of incorrectly connected KTY temperature sensor
If a KTY temperature sensor is connected with incorrect polarity, it is not possible to detect
when the motor overheats. Overheating can cause damage to the motor.
● Connect a KTY temperature sensor with the correct polarity.
Supplementary component descriptions
Manual, 06/2019
Function
Function
1x2- / 2x2-wire
3 and 4-wire
+Temp
+
(channel x)
(Channel x)
-Temp
-
(channel x)
(Channel x)
+Temp
+ I
c
(channel y)
(constant current, positive
channel x)
-Temp
- I
c
(channel y)
(constant current, nega‐
tive
channel x)
Channel assignment
Channel number [x]
for 1x2, 3 and 4-wires
0
1
2
3
4
5
5.3 Terminal Module TM150
Technical data
Temperature sensor connection for sensors with
1x2 wires
Connection of the 2nd measurement cable for
sensors with 4 wires
Temperature sensor connection for sensors with
1x2 wires
Connection of the 1st measurement cable for
sensors with 3 and 4 wires
Temperature sensor connection for sensors with
2x2, 3 and 4-wires
Channel number [y]
for 2x2 wires
6
7
8
9
10
11
Terminal Modules