Amount Of Heat Generated By The Inverter - Mitsubishi Electric 800 Series Hardware Instruction Manual

Separated converter type
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Vibration, impact
The vibration resistance of the inverter is up to 2.9 m/s
Y, Z axes. Applying vibration and impacts for a long time may loosen the structures and cause poor contacts of connectors,
even if those vibration and impacts are within the specified values.
Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.
Countermeasure
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from the sources of the vibration.
2.3.2

Amount of heat generated by the inverter

 Installing the heat sink inside the enclosure
When the heat sink is installed inside the enclosure, the amount of heat generated by the inverter unit and converter unit is
shown in the following tables.
Converter FR-CC2-
H[]
315K
355K
400K
450K
500K
560K
630K
Inverter FR-A842-[]
315K
355K
400K
450K
500K
NOTE
• * The amount of heat generated shown assumes that the output current is the inverter rated current, and the carrier frequency
is 2 kHz.
26
2. INSTALLATION AND WIRING
2.3 Installation of the inverter and enclosure design
Amount of heat
generated (W)
2350
2600
3050
3400
3800
4400
4920
Amount of heat generated (W)
SLD
LD
5800
5050
4450
6690
5800
5100
7370
6480
5650
8600
7340
6500
9810
8630
7400
2
at 10 to 55 Hz frequency and 1 mm amplitude for the directions of X,
ND
HD
3900
4410
4930
5650
6490