Mitsubishi Electric 800 Series Hardware Instruction Manual page 42

Separated converter type
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• Inverter (HD rating)
Inverter
Terminal
Tightening
model FR-
screw
*4
A842-[]
size
07700(315K) M12 (M10)
46
08660(355K) M12 (M10)
46
09620(400K) M12 (M10)
46
10940(450K) M12 (M10)
46
12120(500K) M12 (M10)
46
*1
The recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable), etc.) with continuous
maximum permissible temperature of 90°C or higher. It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.
*2
It is the gauge of the cable with continuous maximum permissible temperature of 90°C (THHN cable). It assumes a surrounding air temperature
of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to
*3
The recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C. It assumes a
surrounding air temperature of 40°C or lower and in-enclosure wiring.
(Selection example mainly for use in Europe.)
*4
The screw size for terminals R/L1, S/L2, T/L3, U, V, W, P/+, N/-, and the earthing (grounding) terminal are shown.
Screw size for earthing (grounding) is indicated in parentheses.
The line voltage drop can be calculated by the following formula:
× wire resistance [mΩ/m] × wiring distance [m] × current [A]
Line voltage drop [V] =
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
NOTE
• Tighten the terminal screw to the specified torque.
A screw that has been tightened too loosely can cause a short circuit or malfunction.
A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
• Use crimp terminals with insulation sleeves to wire the power supply and motor.
Crimp
terminal
torque
(N·m)
U, V, W
U, V, W
150-12
2×125
150-12
2×150
C2-200
2×200
C2-200
2×200
C2-250
2×250
page
1000
Cable gauge
2
*1
HIV cables, etc. (mm
)
Earthing
P/+, N/-
(grounding)
cable
2×150
100
2×150
100
2×200
100
2×200
100
2×250
100
130.)
AWG/
PVC cables, etc. (mm
*2
MCM
Earthing
U, V, W
U, V, W
(grounding)
cable
2×250
2×120
150
2×300
2×150
150
2×350
2×185
2×95
2×400
2×185
2×95
2×500
2×240
2×120
2. INSTALLATION AND WIRING
2.5 Main circuit terminals
1
2
*3
)
2
3
4
5
6
7
8
9
10
41