Main Circuit Terminal Layout And Wiring To Power Supply And Motor - Mitsubishi Electric 800 Series Hardware Instruction Manual

Separated converter type
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.5.3
Main circuit terminal layout and wiring to power
supply and motor
Converter unit
R1/L11 S1/L21
Charge lamp
Jumper
R/L1
S/L2
Power supply
NOTE
• Make sure the power cables are connected to the R/L1, S/L2, and T/L3 of the converter unit. (Phase need not be matched.)
Never connect the power cable to the U, V, and W of the inverter. Doing so will damage the inverter.
• Connect the motor to the U, V, and W of the inverter. (The phases must be matched.)
• When wiring cables to the main circuit conductor, tighten each nut from the right of the conductor as seen from the front of the
unit.
When wiring two cables, place cables on both sides of the conductor. (Refer to the diagram below.)
For wiring, use bolts (nuts) provided with the inverter.
• When wiring the main circuit conductor (R/L1, S/L2, T/L3) of the converter unit (FR-CC2), use bolts (nuts) for wiring the main
circuit before the conductor.
FR-CC2-H315K, H355K
Connect the cables here.
N/-
P/+
T/L3
To inverter
FR-CC2-H400K to H500K
Connect the cables here.
Inverter
R1/L11 S1/L21
N/-
P/+
To converter
unit
2. INSTALLATION AND WIRING
Charge lamp
Jumper
M
Motor
39
2.5 Main circuit terminals
1
2
3
4
5
6
7
8
9
10