Restart - Panasonic Alert annunciation unit 1736 Technical Description

Table of Contents

Advertisement

9

Restart

The AA unit will restart:
When the unit is powered up
If the jumper "JP1" is shunted momentarily
After address setting (i.e. "P2" is pressed).
If the contact with the Control unit is OK again after:
"No contact with Control unit".
During the restart the LCD will display the following (no back-light):
"Checking program memory..."
followed by (very quickly)
"Program memory OK."
followed by
"SSD memory OK."
All LEDs will be turned "ON" during the restart.
If there is a program memory fault, a fault message will be shown in the
display:
"Memory fault in program area (n)"
The AA unit will not work.
A fault message will also be shown in the C.I.E.:
In system FT512:
"FAULT: Comm, AAU xx, 1587 board x, CU xx".
In system FT128:
"FAULT: No reply AAU x".
In system FT1020G3:
"FAULT: No reply, alert annunciation unit ##, control unit ##"
If there is an SSD (Site Specific Data) memory fault or no SSD downloaded,
there will be a fault message in the display:
"SSD memory fault"
The AA unit will work since the alarm texts will be sent out from the C.I.E.
Technical Description
(n=1 or 2).
19
AAU 1736 – Rev 1

Advertisement

Table of Contents
loading

Table of Contents