Advertisement

5 SETTINGS
ÖØ
PATH: SETTINGS
SYSTEM SETUP
BREAKER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
BREAKER 2
UCA SBO TIMER
A description of the operation of the breaker control and status monitoring features is provided in the HUMAN INTER-
FACES chapter. Only information concerning programming of the associated settings is covered here. These features are
provided for two breakers; a user may use only those portions of the design relevant to a single breaker, which must be
breaker No. 1.
BREAKER 1 FUNCTION:
Set to "Enable" to allow the operation of any breaker control feature.
BREAKER1 PUSH BUTTON CONTROL:
Set to "Enable" to allow faceplate push button operations.
BREAKER 1 NAME:
GE Power Management
ÖØ
Ö

BREAKERS

BREAKER 1(2)
BREAKER 1
FUNCTION: Disabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
BREAKER 1 NAME:
Bkr 1
BREAKER 1 MODE:
3-Pole
BREAKER 1 OPEN:
Off
BREAKER 1 CLOSE:
Off
BREAKER 1 φA/3-POLE:
Off
BREAKER 1 φB:
Off
BREAKER 1 φC:
Off
BREAKER 1 EXT ALARM:
Off
BREAKER 1 ALARM
DELAY:
0.000 s
BREAKER 1 OUT OF SV:
Off
MANUAL CLOSE RECAL1
TIME:
0.000 s
As for Breaker 1 above
UCA SBO TIMEOUT:
30 s
L90 Line Differential Relay
5.3 SYSTEM SETUP
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to 6 alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 1 000 000.000 s in steps of 0.001
Range: FlexLogic™ operand
Range: 0.000 to 1 000 000.000 s in steps of 0.001
Range: 1 to 60 s in steps of 1
5.3.6 BREAKERS
5
5-31

Advertisement