GE UR Series Instruction Manual page 198

Line differential relay
Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
b) PHASE OV1 (PHASE OVERVOLTAGE: ANSI 59P)
ÖØ
PATH: SETTINGS
GROUPED ELEMENTS
PHASE
OVERVOLTAGE1
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a Definite
Time element. The input voltage is the phase-to-phase voltage, either measured directly from Delta-connected VTs or as
5
calculated from phase-to-ground (Wye) connected VTs. The specific voltages to be used for each phase are shown on the
logic diagram.
SETTING
PHASE OV1
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
PHASE OV1
SOURCE:
Sequence=ABC Sequence=ACB
VAB
VAC
VBC
VCB
VCA
VBA
SETTING
PHASE OV1
BLOCK:
Off = 0
5-114
Ö
SETTING GROUP 1(8)
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE OV1
MESSAGE
PICKUP: 1.000 pu
PHASE OV1 PICKUP
MESSAGE
DELAY:
PHASE OV1 RESET
MESSAGE
DELAY:
PHASE OV1 BLOCK:
MESSAGE
Off
PHASE OV1
MESSAGE
TARGET: Self-reset
PHASE OV1
MESSAGE
EVENTS: Disabled
SETTING
PHASE OV1
PICKUP:
AND
RUN
V ≥ PICKUP
AND
RUN
V ≥ PICKUP
AND
RUN
V ≥ PICKUP
Figure 5–57: PHASE OV1 SCHEME LOGIC
L90 Line Differential Relay
ÖØ
VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2,..., SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: FlexLogic™ Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTINGS
PHASE OV1 PICKUP
DELAY:
PHASE OV1 RESET
DELAY:
t
PKP
t
RST
t
PKP
t
RST
t
PKP
t
RST
5 SETTINGS
ÖØ
PHASE OVERVOLTAGE1
FLEXLOGIC
OPERANDS
PHASE OV1 A PKP
PHASE OV1 A DPO
PHASE OV1 B PKP
PHASE OV1 B DPO
PHASE OV1 C PKP
PHASE OV1 C DPO
PHASE OV1 A OP
PHASE OV1 B OP
PHASE OV1 C OP
PHASE OV1 PKP
OR
OR
PHASE OV1 OP
827066A2.VSD