Submenu
Language
(language used on the interface)
Set PV (4-20mA)
(primary value measured on the
4-20 mA current loop)
PV Unit
(measurement unit for the primary
value)
Empty/Zero
(distance between the process
connection and the starting point of
the measuring level range)
Full/Span
(the distance between the minimum
level and the maximum level)
Application Category
(general type of process application)
Max Level Rate
(rate at which the vessel should reach
its maximum level)
Display Line1 View1
(first line of text on the first screen
displayed, under the measured value)
All menus available in your LWT instrument are explained in more details in the accompanying user's
guide.
4
Initial software setup
Default value
English
Level
m (meter)
factory-set based on instrument
ordered
factory-set based on instrument
ordered
Water-based (DC>10)
No Filter
Level
Available values
English
French (Français)
German (Deutsch)
Simplified Chinese
Level
Distance
Ullage
m (meter)
cm (centimeter)
mm (millimeter)
ft (feet)
in (inches)
Customizable
Customizable
Water-based (DC>10)
Liquid mix. (3<DC<10)
Oil-based (DC<3)
Solid (organic)
Solid (others)
No Filter
Very Slow: <1cm/min
Slow: <5cm/min
Medium: <25cm/min
Fast: 1m/min
Very Fast: <5m/min
Level
Ullage
PV Percent
Current
Empty
Distance
Span
Probe Length
Media Level

Advertisement