Panasonic U-16GE2E5 Test Run Manual page 21

Gas heat pump air conditioner 2way multi / w multi
Table of Contents

Advertisement

The red LED (D052) lights up, indicating a TEST/WARNING. In this condition, use the UP (S005) or DOWN (S006)
key to select the gas type.
* The relationship between display and gas type is shown in the following table.
↑ UP key
(S005)
↓ DOWN key
(S006)
After completing the selection of gas type, press the SET (S007) key for longer than 1 second. The red LED
(D052) is turned off.
Press the HOME (S004) key to complete the setting operation.
When propane is used, carry out the procedure as described above, and change the setting to "      ".
Display
     (GAS 00)
     (GAS 01)
     (GAS 02)
     (GAS 03)
     (GAS 04)
     (GAS 05)
     (GAS 06)
     (GAS 07)
     (GAS 08)
     (GAS 09)
     (GAS 0A)
     (GAS 0b)
    (GAS 0C)
     (GAS 0d)
     (GAS 0E)
     (GAS 0F)
II - 13
Gas type
Band P (LPG)
No Use
Band H (Natural Gas)
Band L (Natural Gas)
Band (Natural Gas)
No Use
No Use
No Use
No Use
No Use
No Use
No Use
No Use
No Use
Band LNG (Natural Gas)
No Use