Panasonic U-16GE2E5 Test Run Manual page 25

Gas heat pump air conditioner 2way multi / w multi
Table of Contents

Advertisement

The red LED (D052) lights up, indicating a TEST/WARNING. In this condition, press the UP (S005) or DOWN
(S006) key to select the connection number.
* The indication becomes as shown below.
* Setting range
• W MULTI: From 1 to 48 units.
(However, more than 24 indoor units cannot be connected when only a single outdoor unit is installed.)
↑ DOWN key (S006)
↓ UP key (S005)
After completing the selection of the number of connected indoor units, press the SET (S007) key for longer than
1 second.
The TEST/WARNING indicator (red LED (D052)) goes out.
Press the HOME (S004) key for longer than 1 second to complete the setting operation.
Indication
    (in 01)
    (in 02)
    (in 48)
II - 17
Meaning
Number of indoor units connected: 1
Number of indoor units connected: 2
Number of indoor units connected: 48