What other data is transferred over the network?
Network configuration
For each DMS-PC and Ethernet Port we need to know:
IP-Address
–
Subnet mask
–
Default Gateway
–
Note: IP addresses must be static (DHCP not supported).
Who is the responsible person for the IP-addresses and router configuration?
Is a remote access necessary?
If yes, how? (IntERnet IntRAnet, dial-up)
Firewall configuration:
Are the necessary ports open?
TCP Port number 3001 (NK82xx)
TCP Port 3001...3004 (Multiple host configurations)
TCP Port 4000 (NK82xx)
TCP Port 20,500 (Secure download)
TCP Port 20, Port 21 (FTP)
TCP Port 22 (SSH Secure Shell)
TCP Port 80 (HTTP for MM8000 Web Server, Web Services)
TCP Port 443 (HTTPS for MM8000 Web Server, Web Services)
TCP Port 502 (Modbus)
UDP Port 53 (DNS Service, Traceroute from NK823x)
UDP Port 161 (SNMP)
UDP Port 47808 (BACnet)
Availability
Does the customer specify the network availability?
Are there special requirements regarding error/failure rate?
If yes, what are the requirements?
Is the power supply of the network components backed up by a UPS?