Dv/dt filter compact plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

General
Burns due to high surface temperature of the dv/dt filter compact
The surface temperature of the dv/dt filters compact may exceed 80 °C. You can get
seriously burnt when touching the surface.
• Mount the dv/dt filters compact so that they cannot be touched. If this is not possible,
NOTICE
Damage to the Voltage Peak Limiter due to interchanged connections
The Voltage Peak Limiter will be damaged if the input and output connections are
interchanged on devices with the article numbers 6SL3000-2DE41-4EA0 and 6SL3000-
2DG38-1EA0.
• Connect the incoming cable from the DC link of the Power Module to DCPS, DCNS.
• Connect the outgoing cable for the dv/dt reactor to 1U2, 1V2, 1W2.
NOTICE
Damage to the dv/dt filter compact by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use a dv/dt filter compact that SIEMENS has released for operation with
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum output frequency
The maximum permissible output frequency when using a dv/dt filter compact is 150 Hz.
The dv/dt filter compact can be damaged if the output frequency is exceeded.
• Operate the dv/dt filter compact with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dv/dt filter compact during continuous operation with low output frequencies
Uninterrupted duty at an output frequency less than 10 Hz can result in thermal overload
and destroy the dv/dt filter.
• When using a dv/dt filter compact plus voltage peak limiter do not operate the drive
• You may operate the drive for a maximum load duration of five minutes at an output
12
CAUTION
attach a clearly visible and understandable warning notice at hazardous positions.
SINAMICS.
continuously with an output frequency less than 10 Hz.
frequency less than 10 Hz, provided that you then select an operation with an output
frequency higher than 10 Hz for a period of five minutes.
dV/dt filter compact plus Voltage Peak Limiter