NOTICE
Damage to the dv/dt filter compact by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using a dv/dt filter compact is 2.5 kHz or
4 kHz. The dv/dt filter compact can be damaged if the pulse frequency is exceeded.
• When using the dv/dt filter compact, operate the Power Module with a maximum pulse
NOTICE
Damage to the dv/dt filter compact if it is not activated during commissioning
The dv/dt filter compact may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter compact during commissioning via parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter compact if a motor is not connected
dv/dt filters compact which are operated without a motor being connected can be damaged
or destroyed.
• Never operate a dv/dt filter compact connected to the Power Module without a
Note
Cable lengths
Keep the connecting cables to the Power Module as short as possible (max. 5 m). Use an
equivalent cable type when replacing the cables supplied.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 11/2017, A5E02590131A
frequency of 2.5 kHz or 4 kHz.
connected motor.