Download Print this page

Siemens SINAMICS G130 Operating Instructions Manual page 37

Dv/dt filter compact plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

Table 6- 5
Technical data for the dv/dt filter compact plus Voltage Peak Limiter, 3 AC 500 V ... 600 V, part 2
Article number
Suitable for Power Module
Unit rating of the Power
Module
I
thmax
Degree of protection
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Terminals
- 1U1/1V1/1W1
- DCPS/DCNS
- 1U2/1V2/1W2
- PE
Max. permissible cable
length between dV/dt filter
and motor
Dimensions
Width
Height
Depth
Weight, approx.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 11/2017, A5E02590131A
6SL3000-
2DG35-8EA0
6SL3310-
1GF34-7AA3
1GF35-8AA3
kW
315
400
A
575
IP00
kW
0.571
kW
0.586
kW
0.689
for M12 bolt
for M8 bolt
for M12 bolt
M6 screw
m
mm
440
mm
369
mm
311
kg
100
Technical specifications
100 (shielded)
150 (unshielded)
35

Advertisement

loading