5.5 Error Reset

In case of FN module error down, analyze the error and resolve the problem. The FN
module can now be restarted. There are two ways of error reset as follows.
• Error reset using the Engineering Tool
• Switching power back on
Error Reset with the Engineering Tool
(1) Select [Station Configuration] from [Product View] on the Engineering Tool. The
[Configuration Editor] window opens.
(2) Open the [Display] menu from the Configuration Editor] window, and select [Control
Panel].
(3) Select [RUN] from the [Control Panel] menu.
(4) Select Primary/Secondary from [Control Instruction], then select [Error reset], and
click [OK].
Error Reset by Switching Power Back On
(1) In case of a C-module, for example, that has a shutdown sequence, start that
sequence.
(2) Switch power off.
(3) Wait for 3 seconds or more after all the LEDs have gone out, then switch power back
on.
Note: If the error remains unremedied, the error down occurs again. In such a case,
remedy the error completely before taking the above steps.