Ethernet Transmission Specifications - Toshiba V Series Operation Manual

Integrated controller, ethernet module / ds connection module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

A.2 Ethernet Transmission Specifications
Item
Applicable standard
Media access
Data transmission speed
Ethernet frame
Topology
Ethernet frame
Transmission path
Transmission cable/cable
length
Segment
No. of nodes
No. of repeaters
No. of EN7 modules
Interface
Note: It applies to the specifications of an application system correspondingly.
(ex. TOSDIC-CIE 1200, the numbers of nodes are a maximum of 64 nodes.)
6F8C0878
Table A-3 Ethernet Transmission Specifications
IEEE802. 3
• 10BASE5
• 10BASE2
• 10BASE-T
IEEE802. 3u
• 100BASE-TX
CSMA/CD
10Mbps/100Mbps
DIX type
Bus
DIX format
Single bus
Dual bus
EN711, EN721 (10BASE5)
• Yellow cable for Ethernet: 500 m maximum
(Coaxial cable: Characteristic impedance 50 ohms)
• AUI cable: 15 m maximum
Recommended cable
AUI15 –[ ] M (Showa Electric Wire & Cable Co., Ltd.)
EN731, EN741 (10BASE2)
• 3D-2V (as drop cable or for indoor use)
• 5D-2W (as trunk cable or for use from indoor to control room): 185 m maximum
EN751, EN751A, EN761 (100BASE-TX/10BASE-T)
• Category 5 twisted pair cable : 100m maximum
FN711 (100BASE-TX/10BASE-T)
• Category 5 twisted pair cable : 30m maximum
5 segments maximum between nodes
Of the 5 segments, 3 cable segments maximum
126 nodes maximum per system (or as per the system specifications of TOSDIC-
CIE 1200 when applied to TOSDIC-CIE 1200)
100 nodes maximum/segment : 10BASE5
30 nodes maximum/segment : 10BASE2
(node includes repeater)
4 repeaters maximum per system
4 modules maximum per base unit (Multiport)
EN711, EN721 (10BASE5)
15-pin D-sub connector (socket) with slide lock
EN731, EN741 (10BASE2)
BNC connector
EN751, EN751A, EN761, FN711 (100BASE-TX/10BASE-T)
RJ-45 connector
A.2 Ethernet Transmission Specifications
Specifications
A
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents