PDU8000 Isolation Transformer Cabinet
User Manual
After the installation is complete, check the items listed in the following table before
powering on the equipment. The equipment can be powered on only after passing the check.
Table 6-1 Check before power-on
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Issue 01 (2019-03-07)
6
Check Item
All cables are correctly connected based on the
Schematic Diagram.
Ground cables are securely connected.
Redundant parts of the ground cables and power cables
are cut off instead of coiled.
Phase cables are connected properly.
Power cables and ground cables are routed and bundled
separately from other types of cables.
All circuit breakers are OFF.
The cabinet is clean, without dust or sundries.
The paint on the cabinet exterior is intact. If paint flakes
off, repaint that area immediately to avoid corrosion.
The cabinet door and lock work properly.
All labels are correct, clear, and complete.
The surrounding area of the cabinet contains no waste
tape, cable ties, paper, or packing materials.
All bolts are tightened, especially the bolts used for
electrical connection. Flat washers and spring washers
are installed properly in the correct sequence.
Cables are bundled neatly, and cable ties are secured
evenly and properly in the same direction.
Cables are routed for ease of future maintenance and
expansion.
Copyright © Huawei Technologies Co., Ltd.

Check Before Power-On

6 Check Before Power-On
Check Result
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed