Data On Rs485 Serial Communication Module Cable - ABB Relion 670 Series Installation Manual

Version 2.2 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Connecting
ExV is supplied by the Node at end of the Bus Segment
The specifications of the components are:
2.3.3
The end node in each Ph-segment applies 5 V bus excitation power to the Termination
network via the Excitation pair (ExV+ and GND) used in the Type 3 Physical layer
specification.
6.4.3

Data on RS485 serial communication module cable

Type:
Shield:
Length:
Temp:
Impedance:
Capacitance:
Example:
72
ExV+
Signal B
Signal A
DGND
ExV is supplied by the Node at end of the Bus Segment
IEC03000112 V1 EN-US
Figure 51:
RS-485 bus segment termination
a) Ru
+ 5 V to Signal B
b) Rt
Signal B to Signal A
c) Rd
Signal A to GND
Bus power distribution
Twisted-pair S-STP (Screened – Screened Twisted Pair)
Individual foil for each pair with overall copper braid
Maximum 1200 m (3000 ft) from one system ground to the next system ground (includes
length from platform point to system ground on both sides)
According to application
120 W
Less than or equal to 42 pF/m
Belden 9841,Alpha wire 6412, 6413
Ru = 390 ohm
1/4 W, 2%
Rt = 220 ohm
1/4 W, 2%
Rd = 390 ohm
1/4 W, 2%
en03000112.vsd
= 390 W, 0.25 W ±2.5%
= 220 W, 0.25 W ±2.5%
= 390 W, 0.25 W ±2.5%
1MRK 514 026-UUS F
SEMOD176342-280 v2
670 series
Installation manual