The following parameter settings for the channels are possible:
Table 4- 2
Configurable parameters and their defaults
Parameters
Diagnostics
Overflow
•
Underflow
•
Common mode error
•
Wire break
•
1)
Measuring
Measuring type
•
Measuring range
•
Temperature coefficient
•
Temperature unit
•
Interference frequency
•
suppression
Smoothing
•
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Manual, 03/2019, A5E44792324-AA
Range of values
Default
setting
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
See chapter Meas-
Voltage
uring types and
±10 V
ranges (Page 18)
Pt: 0.003851
0.003851
Pt: 0.003902
Pt: 0.003916
Pt: 0.003920
Ni: 0.00618
Ni: 0.00672
LG-Ni: 0.005000
°C
Kelvin (K)
•
Fahrenheit (°F)
•
Celsius (°C)
•
400 Hz
50 Hz
60 Hz
50 Hz
10 Hz
None/low/medium/hi
None
gh
Parameters/address space
Parameter as-
Scope with configuration software,
signment in
e.g., STEP 7 (TIA Portal)
RUN
GSD file
PROFINET IO
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
4.2 Parameters
GSD file
PROFIBUS DP
Module
2)
Module
2)
Module
2)
Module
2)
Channel
Channel
Channel
Module
Module
Channel
21