Siemens SIMATIC ET 200MP Manual page 33

Analog input module ai 8xu/i/r/rtd ba
Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

Interrupts/diagnostics alarms
5.1 Status and error displays
Meaning of the LED displays
The following tables explain the meaning of the status and error displays. Remedial
measures for diagnostic alarms can be found in section Diagnostic alarms (Page 35).
RUN and ERROR LED
Table 5- 1
Status and error displays RUN and ERROR
LEDs
RUN
ERROR
Voltage missing or too low at backplane bus.
Off
Off
The module starts and flashes until the valid
parameter assignment is set.
Flashes
Off
Module is configured.
On
Off
Indicates module errors (at least one error at
one channel, e.g., wire break).
On
Flashes
Hardware defective.
Flashes
Flashes
CHx LED
Table 5- 2
CHx status display
LED CHx/COMP
Channel disabled
Off
Channel configured and OK.
On
Channel is configured (channel error pending).
Diagnostic alarm: e.g. wire break
On
32
Meaning
Meaning
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Remedy
Switch on the CPU and/or the system power
supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are insert-
ed.
---
Evaluate the diagnostics data and eliminate the
error (e.g., wire break).
Replace the module.
Remedy
---
---
Check the wiring.
Disable diagnostics.